Littelfuse M1000 Series User Manual

M1000 series, Engine control, Alarm monitoring

Advertising
background image

Engine Control

© 2013 Littelfuse Protection Relays & Controls

Alarm Monitoring

Monitoring

M1000 SerieS

Alarm Monitor

Ordering

nuMber

cOntrOl

pOwer

FunctiOn

M1000.0040

48-110 Vdc

IP54 front

M1000.0080

12-24 Vdc

IP54 front

M1000.0220

12-24 Vdc

Internal siren, IP54 at front

Description

The M1000 is an alarm panel with 10 digital inputs. Inputs from
a dry contact (normally open [NO] or normally closed [NC])
will cause the corresponding LED to flash. Simultaneously a
common alarm output and a siren output will be activated as
well as an individual output. The unit has separate indications
of first alarm, following alarms and acknowledged alarms. It
also has dedicated inputs for remote reset and blocking. The
unit can be configured for cable monitoring and monitoring of
its own supply and insulation level.
Multiple M1000 units can be interconnected to form a large
scale alarm system. In this situation functions are available
for synchronizing the flashing of the LEDs and enabling
global indication of first alarm for all connected units. Alarm
related parameters like time delays, reset functions and other
features can be configured through 18 programming switches.
The M1000 can also be configured via the RS232 interface.
A standard ANSI/VT100 terminal is used as programming
tool. The M1000 is equipped with a 2-wire RS485 interface
supporting MODBUS-RTU communication.

Ordering Information

Simplified Circuit Diagram

FeatureS

beneFitS

10 configurable

digital inputs

Supports both NO and NC input contacts

11 open collector outputs

Allows external control and remote indication

1 siren relay output

Direct connection of alarm siren

Special indication of

first alarm

Provides clear alarm overview in

larger systems

Multiple units can be

connected as one system

Modular and scalable solution

Voltage and insulation

monitoring

Replaces voltage and insulation monitoring

relay on the DC system

Dimming of LEDs

Suitable for bridge consoles

Type-approved by marine

classification societies

Applicable in harsh environments

Configuration by

DIP switches or PC

Easy installation and configuration

RS485 Modbus RTU

Communication with HMI and

SCADA systems

Features & Benefits

Specifications

Voltage Supply

12-24 Vdc-30%/+30% (8-32 Vdc)

48-110 Vdc-30%/+40% (33-155 Vdc)

Max. Power

Consumption

180 mA

Ambient Temp.

–10°C to +70°C (also available for –40°C to +70°C)

Siren Relay Contact 220 Vac/2 A; 30 Vdc/2 A, 30 W
Output

Max. 150 mA per channel

Resistance in

Sensing Cable

Max. 1000 W

Insulation Monitor 25 kW±8 kW (50 kW±10 kW for M1000-11-XXC)
Impulse Test

4.5 kV

1

/

50

μsec.

EMC

CE according to EN50081-1, EN50082-1,

EN50081-2, EN50082-2 and EN61000-2-6

Programming

16 dip-switches or via RS232 interface

Communication

RS485 interface

Weight

0.4 kg

Dimensions

H 144 mm (5.7”); W 144 mm (5.7”);

D 35 mm (1.4”)

Panel Cut-out

H 138 mm (5.4”); W 138 mm (5.4”)

Protection Degree

at Front

IP54 (see Type Description)

www.littelfuse.com/m1000

17

26

10

28

29

30
31
32

11

12
13

1

+

TEST

BLOCK

M1000

(Alarm Monitor)

SUPPLY

SIREN

OPEN

COLLECTOR

OUTPUTS

ALARM

INPUT

CONTACTS

RESET

Rev: 4-A-050313

Advertising