Littelfuse PGR-3200 Series User Manual

Pgr-3200 series, Protection relays & controls, Ground-fault protection – ungrounded ac system

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Littelfuse.com/pgr-3200

Ground-Fault Protection – Ungrounded AC System

A

PGR-3100

UNGROUNDED

SUPPLY

B

C

A

L2

PGR-3200

L1

B

C

(Ground-Fault

Indication System)

(Ground-Fault

Protection System)

PGR-3200 SeRieS

Ground-Fault Protection System

Description

The PGR-3200 detects ground faults by continuously

monitoring the insulation integrity of ungrounded electrical

systems. The relay monitors the insulation for damage and

assists with predictive maintenance and troubleshooting of

developing ground faults by providing two warning and an

alarm level. The PGR-3200 operates on one- or three-phase

ungrounded systems up to 6 kV.
The PGR-3200 can also be used on a grounded system to

monitor the insulation for damage, while the power system

is de-energized. The mode-of-operation terminals (27-28)

are connected to the circuit breaker or contactor auxiliary

contacts to toggle the relay off when the contactor or breaker

is closed.

Specifications

IEEE Device Numbers

Undervoltage Relay (27)

Ground Detector Relay (64)

Input Voltage

See ordering information

Dimensions

H 75 mm (3”); W 100 mm (3.9”); D 110 mm (4.3”)

Resistance Ratings

Insulation warning (30 kΩ

and 50 kΩ

)

Insulation alarm

(10 kΩ

)

Contact Operating Mode Non-fail-safe

Test Button Local

Reset Button

Local and remote

Output Contacts

Two Form C

Analog Output

0-1 mA

Conformally Coated

Consult factory

Warranty

5 years

Mounting

DIN, Surface

ORdeRinG nUmbeR

COntROl POweR

PGR-3200

240 Vac

PGR-3200-120

120 Vac

Ordering Information

Simplified Circuit Diagram

Note: For optional conformal coating please consult factory. To convert to a resistance

grounded system, see neutral-grounding-resistors packages.

PGH Series High-Tension Coupler

A PGH Series high-tension coupler is required

for systems between 1,300 V and 6,000 V.

PGA-0510 Analog Ohm Meter

Optional PGA-0510 Analog Meter allows

for metering of insulation resistance.

FeAtUReS

beneFitS

NEC

®

and CEC Code

compliant

Meets National Electrical Code (NEC

®

) Article

250.21(B) and Canadian Electrical Code Part 1,

Section 10-106 (2) requirements for ungrounded

systems

Output contact

(50 k

Ω

)

Form C output contact for alarming when the

insulation resistance is below 50 k

Ω

Output contact

(10 k

Ω

)

Form C output contact for tripping when the

insulation resistance is below 10 k

Ω

Analog output

(0 - 1 mA)

Provides means for connecting to an optional

meter (PGA-0510) or control system

DIN-rail or surface

mount

Flexible options for ease of installation

Features & Benefits

Accessories

A

A

ACCeSSORieS

ReqUiRement

PGH Series

Required >1,300 V

PGA-0510

Optional

Rev: 4-A-050213

Based on Manual Rev 3a

Advertising