Littelfuse T3300 Series User Manual

T3300 series, Protection relays & controls, Features & benefits

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Features & Benefits

Littelfuse.com/t3300

Generator & Single-Function Protection–Voltage

T3300 SerieS

3-Phase Voltage Relay

Description

The T3300 Voltage Relay is designed for voltage monitoring

on generators, bus bars or other distribution systems. The

T3300 will signal when the voltage is under or over the

limits for a preset time period.
The T3300 consists of two circuits, one circuit for

overvoltage and one for undervoltage monitoring.

Each circuit has individual settings for voltage levels and

time delays.

Specifications

Overvoltage Level

100-120%

Delay

1-10 sec.

Hysteresis

1-10%

Undervoltage Level

80-100%

Delay

1-10 sec.

Hysteresis

1-10 %

Max. Voltage

660 V

Voltage Range

70-120%

Consumption

5 VA at U

N

Frequency Range

40-400 Hz

Overvoltage Relay

Normally de-energized

Undervoltage Relay

Normally energized

Contact Rating

AC: 250 V, 2 A, 250 VA

DC: 60 V, 2 A, 100 W

Overall Accuracy

±3% of highest value

Repeatability

±1%

Operating Temperature –20°C to + 70°C

Dielectric Test

2500 V, 50 Hz

EMC

CE according to EN50081-1, EN50082-1, EN50081-2,

EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate. Flame retardant

Weight

1.2 kg

Dimensions H

70 mm (2.76”); W 150 mm (5.9”); D 115 mm (4.52”)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

Ordering Information

Simplified Circuit Diagram

Other voltages are available on request.

Features & Benefits

OrderinG number

TerminalS

17-19

21-23

25-27

18-19

22-23

26-27

T3300.0010

230 V

T3300.0020

450 V

400 V

T3300.0030

110 V

100 V

T3300.0040

480 V

415 V

16
15
14

12
11
10

OVERVOLTAGE

ALARM

(Inputs are isolated)

UNDERVOLTAGE

ALARM

PHASE

1

PHASE

2

PHASE

3

22

23

21

26

27

25

18

19

17

T3300

(Voltage Relay)

FeaTureS

beneFiTS

Accepts high supply

voltage variation

Ensures correct operation in spite of voltage

supply fluctuations (fulfills marine class

requirement)

Visual indication of power,

pick-up, and output trip

Provides quick and concise status information

Direct line-line or line-

neutral voltage supply (up

to 690 Vac)

Simplifies design and installation.

No need for PTs.

Combining 2 relays in

same enclosure

Economic solution. 3-phase monitoring of both

undervoltage and overvoltage in same unit,

and occupying less space in the switch panel

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN-rail or screw-mount

& adjustment by

potentiometers

Easy installation

Rev: 4-A-050213