Description

The SE-701 is a microprocessor-based ground-fault relay for resistance-

and solidly-grounded systems. In addition to common systems, it is

uniquely suited for use on systems with significant harmonic content.

The SE-701 can provide main-plant protection, feeder-level protection,

or individual-load protection. Proper current transformer selection

provides the desired pickup range. The output contacts can be

connected for use in protective tripping circuits or in alarm indication

circuits. The analog output can be used with a PLC or a meter.

SE-701 SEriES (PGr-5701)

Ground-Fault Monitor

Specifications

IEEE Device Numbers

Ground fault (50G/N, 51G/N)

Input Voltage

See ordering information

Dimensions

H 75 mm (3.0"); W 55 mm (2.2"); D 115 mm (4.5")

Trip Level Settings

1-99% CT-Primary Rating

Trip Time Settings

0.05-2.5 s

Contact Operating Mode Selectable fail-safe or non-fail-safe

Harmonic Filtering

Standard feature

Test Button

Standard feature

Reset Button

Standard feature

CT-Loop Monitoring

Standard feature

Output Contacts

Isolated Form A and Form B

Approvals

CSA certified, UL Listed (E340889),

CE (European Union), C-Tick (Australian)

Analog Output

0-5 V

Conformally coated

Consult factory

Warranty

5 years

Mounting

DIN, Surface (standard)

Panel (with PMA-55 or PMA-60 adapter)

OrdErinG numbEr

cOntrOl POwEr

SE-701-OU

120/240 Vac/Vdc

SE-701-OD

12/24 Vdc

SE-701-OT

48 Vdc

SE-701-O3

24 Vac

Ordering Information

Simplified Circuit Diagram

FEaturES

bEnEFitS

Adjustable pickup

(1-99%)

Trip setting based on input CT primary, allows use with

any CT. Minimum 50 mA with EFCT Series.

Adjustable time delay

(50 ms - 2.5 s)

Adjustable trip delay allows quick protection and system

coordination

Output contacts

Form A and Form B ground-fault output contacts for

operation of separate annunciation and trip circuits

Analog output

(0 - 5 V)

Allows for connecting an optional meter (PGA-0500) or a

control system

CT-Loop monitoring

Alarms when CT is not connected

Selectable DFT or peak

detection filtering

Compatible with variable-speed drives

Harmonic filtering

Eliminates nuisance tripping

Non-volatile trip

memory

Retains trip state while de-energized to simplify

troubleshooting

Microprocessor based

No calibration required, saves on maintenance cost

Universal power supply

Allows operation in application where one side of PT is

faulted, provides flexibility for numerous applications

Features & Benefits

Note: For optional conformal coating please consult factory.

accESSOriES

rEquirEmEnt

Current Transformer

Required

PGA-0500

Optional

PMA-55, PMA-60

Optional

SE-EFVC Voltage Clamp

Optional

Accessories

Ground-Fault Current Transformer

Required current transformer model depends on

application. We offer a variety of sensitive CTs with

5- and 30-A primaries.

PGA-0500 Analog % Current Meter

Optional panel-mounted analog meter displays

ground-fault current as a percentage of the CT

primary rating.

A

B

A

Ground-Fault Protection–Grounded Systems