SE-502 SERIES

Ground-Fault Ground-Continuity Detector

Description

The SE-502 Ground-Fault Ground-Continuity Detector provides

Class-A GFCI trip level and trip times for personnel protection.

As little as 5 mA of ground-fault current can be detected, and the

internal neutral-grounding resistor limits the maximum ground-fault

current to 100 mA. The SE-502 can be used on both energized and

de-energized systems, and will continuously monitor neutral

continuity, detect a load-side grounded neutral, and is capable of

ground proving. These features make the SE-502 ideal for use with

120/208 V portable generators and in heat-trace applications.

Specifications

IEEE Device Numbers

Ground (Earth) Detector Relay (64)

Lockout Relay (86)

Open-Neutral Detector Relay (95)

Input Voltage

120 Vac, 50/60 Hz

Dimensions

H 75 mm (3.0")
W 100 mm (4.0")
D 113 mm (4.4")

Trip Level Settings

5 ± 0.9 mA

Trip Time Settings

Class A GFCI to 25 ms maximum

Contact Operating Mode Trip: fail-safe or non-fail-safe

Alarm: fail-safe

Reset Button

Standard feature plus remote input

Output Contacts

Two Form C

Warranty

5 years

Mounting

DIN, Surface

FEATURES

BENEFITS

Sensitive 5 mA ground-

fault detection

Can be used with an appropriate breaker to

provide Class A GFCI people protection

Internal neutral-

grounding resistor

Limits maximum ground-fault current to 100 mA,

creates a safer system and elminates arc-flash

ground-fault hazards

Neutral-to-ground

connection monitoring

Can detect a hazardous ungrounded condition and

trip or alarm

On- and off-line

monitoring

Can detect a ground fault when the system is

energized or de-energized

Output contacts

Two Form C output contacts for alarming or

tripping purposes

Features & Benefits

Simplified Circuit Diagram

SE-502 SERIES

120-V
Loads

120/208 V

Generator

A

G

B

C

N

(Ground-Fault

Ground-Continuity Detector)

ORDERING NUMBER

CONTROL POWER

SE-502-01

120 Vac

Ordering Information

Ground-Fault Ground-Continuity Detection

Rev: 4-A-050213

Based on Manual Rev 0