Generator & Single-Function Protection–Differential

T2900 SerieS

3-Phase Differential Relay

Description

The T2900 3-Phase Differential Relay is designed for

monitoring current leakage in generators. The T2900

measures the differential current of each of the 3 phases.

The differential currents are measured by connecting a

current transformer for each winding in parallel with inverse

polarity. The highest of the 3 currents is selected and,

if it exceeds the preset level (0.04-0.4 x I

N

), the pick-up

LED will indicate this and the delay timer will be started.

After the preset time has expired, the output relay and

the corresponding LED will be activated, provided that the

current level was exceeded for the entire delay time. The time

delay can be adjusted between 1-10 sec. This time delay can

be reduced by a factor 10 by bridging terminals 18 and 19.

Specifications

Trip Level

0.04-0.4 x I

N

Delay

1-10 sec. (0.1-1 sec. when bridging terminals 18 and 19)

Max. Voltage

660 V

Voltage Range

60-110%

Consumption

Voltage 5 VA at U

N

Current 0.3 VA at I

N

Continuous Current

2 x I

N

Frequency Range

45-400 Hz

Output Relay

Normally de-energized, latching, resetable

Contact Rating

AC: 400 V, 5 A, 2000 VA

DC: 150 V, 5 A, 150 W

Overall Accuracy

±5%

Repeatability

±1%

Operating Temperature –20°C to + 70°C

Dielectric Test

2500 V, 50 Hz

EMC

CE according to EN50081-1, EN50082-1, EN50081-2,

EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate. Flame retardant

Weight

0.5 kg

Dimensions H

70 mm (2.76”); W 100 mm (3.94”); D 115 mm (4.52”)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

Ordering Information

Simplified Circuit Diagram

Standard types: I

N

= 5 A and output relay normally de-energized.

Other combinations and voltages are available on request.

Features & Benefits

OrDerinG number

TerminalS

i

n

1-3

2-3

T2900.0010

450 V

400 V

5 A

T2900.0020

230 V

5 A

T2900.0030

480 V

415 V

5 A

T2900.0040

110 V

100 V

5 A

SUPPLY

DIFFERENTIAL

CURRENT

DEVICE UNDER

PROTECTION

I

1

U

I

2

I

3

2

3

11

12

13

14
15
16

1

10

9

8

7

6

5

19

18

L

1

L

2

L

3

T2900
(3-Phase Differential Relay)

FeaTureS

beneFiTS

Accepts high supply

voltage variation

Ensures correct operation in spite of voltage

supply fluctuations (fulfills marine class

requirement)

Visual indication of power,

pick-up, and output trip

Provides quick and concise status information

Direct line-line or line-

neutral voltage supply (up

to 690 Vac)

Simplifies design and installation.

No need for PTs.

Built-in capacitor

back-up supply

Ensures correct operation in spite of drop in

the supply voltage

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN-rail or screw-mount

& adjustment by

potentiometers

Easy installation

bridge between terminals 5 and 6 results in latching relay.

bridge between terminals 18 and 19 reduces time delay to 0.1-1 sec.