Littelfuse T2000 Series User Manual

T2000 series, Protection relays & controls, Reverse power relay description

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

9

5

C/B TRIP

10

6

L - L SUPPLY

7
8

1

3

2

RESET

13
14

LOAD

1

2

3

L

L

L

T2000

(Reverse

Power

Relay)

G

Littelfuse.com/t2000

Generator & Single-Function Protection–Reverse Power

T2000 SeRieS

Reverse Power Relay

Description

Under parallel operation, the T2000 Reverse Power Relay will

protect the generator from being run as an electric motor. The

T2000 will protect the prime mover of the generator against

physical damage, but will also protect the parallel running

generators from overload caused by the inversed load shift in

a reverse power situation.
The T2000 calculates I x cos F, representing the active

power. If the active power becomes negative and exceeds

the preset level (2-20%), the pick-up LED will indicate

this and the delay timer will be started. After the preset

time (2-20 sec.) has expired, the output relay and LED will

be activated, provided that the reverse power level was

exceeded for the entire delay time.

Specifications

Trip Level

2-20% I

N

Delay

2-20 sec.

Max. Voltage

660 V

Voltage Range

50-110%

Consumption

5 VA at U

N

Continuous Current

2 x I

N

Frequency Range

45-400 Hz

Output Relay

Normally de-energized, latching, resetable

Contact Rating

AC: 400 V, 5 A, 1250 VA

DC: 150 V, 5 A, 120 W

Overall Accuracy

±5%

Repeatability

±1%

Operating Temperature –20°C to + 70°C

EMC

CE according to EN50081-1, EN50082-1,

EN50081-2, EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate. Flame retardant

Weight

0.5 kg

Dimensions H

70 mm (2.76”); W 100 mm (3.94”);

D 115 mm (4.52”)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

ORdeRinG

numbeR

TeRminalS

i

n

SuPPly FuncTiOn

1-3

2-3

T2000.0010

230 V

5 A L-N

T2000.0020

450 V 400 V 5 A L-L

T2000.0030

127 V 120 V 5 A L-N

T2000.0040

110 V 100 V 5 A L-L

T2000.0050

110 V 100 V 5 A L-L

No time delay

T2000.0060

230 V

1 A L-N

T2000.0070

660 V

5 A L-L

T2000.0080

450 V 400 V 5 A L-N

Delay 0.2 - 2.0 sec.

T2000.0090

127 V 120 V 5 A L-L

T2000.0100

110 V 100 V 1 A L-L

T2000.0110

450 V 400 V 5 A L-L

No time delay

T2000.0120

480 V 415 V 5 A L-L

T2000.0130

230 V

5 A L-N

No time delay

T2000.0140

230 V

5 A L-L

T2000.0150

480 V 415 V 1 A L-L

T2000.0160

450 V 400 V 1 A L-L

Ordering Information

Simplified Circuit Diagram

Other supply voltages and combinations are available on request.

FeaTuReS

beneFiTS

Accepts high supply

voltage variation

Ensures correct operation in spite of voltage

supply fluctuations (fulfills marine class

requirement)

Visual indication of

power, pick-up, and

output trip

Provides quick and concise status information

Direct line-line or line-

neutral voltage supply

(up to 690 Vac)

Simplifies design and installation. No need for

PTs or separate power supply

Available with instant

output trip

Enables alternative use for detection of current

direction

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN-rail or screw-mount

& adjustment by

potentiometers

Easy installation

Features & Benefits

Rev: 4-A-050213

Advertising