Littelfuse T2500 Series User Manual

T2500 series, Protection relays & controls, Overcurrent and short-circuit relay description

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Littelfuse.com/t2500

Generator & Single-Function Protection–Overcurrent/Short-Circuit

T2500 SerieS

Overcurrent and Short-Circuit Relay

Description

The combined T2500 3-Phase Overcurrent and Short-Circuit

Relay is used for protection of generators and power

transmissions. The short-circuit relay protects against faults

causing high currents, and the overcurrent relay protects

against thermal damage.

Specifications

Overcurrent Trip Level 0.5-1.4 x I

N

Delay

3-30 sec.

Short-Circuit Trip Level 1.0-4.0 x I

N

Delay

0.1-1.0 sec.

Max. Voltage

660 V

Voltage Range

60-110%

Consumption

5 VA at U

N

Continuous Current

2 x I

N

Frequency Range

45-400 Hz

Output Relay

Normally energized

Extra Output Relay

Normally de-energized

Contact Rating

AC: 400 V, 5 A, 2000 VA; DC: 150 V, 5 A, 150 W

Overall Accuracy

±5%

Repeatability

±1%

Operating Temperature –20°C to + 70°C
EMC

CE according to EN50081-1, EN50082-1, EN50081-2,

EN50082-2
Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate. Flame retardant

Weight

0.5 kg

Dimensions H

70 mm (2.76”); W 100 mm (3.94”); D 115 mm (4.52”)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

OrderinG

number

TerminalS

i

n

FunCTiOn

1-3

2-3

T2500.0010 450 V 400 V 5 A

Latching output, resetable

T2500.0020 230 V

5 A

Latching output, resetable

T2500.0030 480 V 415 V 5 A

Latching output, resetable

T2500.0040 450 V 400 V 1 A

Latching output, resetable

T2500.0050 24 Vdc

5 A

Latching output, resetable

T2500.0060 230 V

5 A

De-energized extra output relay

T2500.0070 450 V 400 V 5 A

De-energized extra output relay

T2500.0080 450 V 400 V 5 A

De-energized extra output relay,

latching outputs

T2500.0090 480 V 415 V 5 A

De-energized extra output relay

T2500.0100 24 Vdc

1 A

De-energized extra output relay

T2500.0110 450 V 400 V 5 A

De-energized extra output relay,

latching short circuit output

T2500.0120 24 Vdc

5 A

De-energized extra output relay,

de-energized relay 1, no internal

power backup

Ordering Information

Simplified Circuit Diagram

Other combinations and voltages are available on request.

Features & Benefits

SUPPLY

SHORT CIRCUIT

OVERCURRENT

I

1

U

I

2

I

3

19

17

18

20

2
3

11

12
13

14
15

16

1

10

9
8
7

6
5
4

L

1

L

2

L

3

T2500

(Overcurrent & Short-Circuit Relay)

FeaTureS

beneFiTS

Accepts high supply

voltage variation

Ensures correct operation in spite of voltage

supply fluctuations (fulfills marine class

requirement)

Visual indication of

power, pick-up, and

output trip

Provides quick and concise status information

Direct line-line or line-

neutral voltage supply

(up to 690 Vac)

Simplifies design and installation.

No need for PTs.

Combining 2 protection

functions in same

enclosure

Economic solution, occupying less space in

the switch panel

Available with extra

output

Economic solution for non-essential load

tripping

Versions available with

separate 24 Vdc supply

Safe operation–Maintains protection

regardless of system voltage failure

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN-rail or screw-mount

& adjustment by

potentiometers

Easy installation

Connection between 20 and 19 gives instant operation of Relay 2.

Connection between 20 and 17 gives delayed operation of Relay 2.

Connection between 20 and 18 gives synchronized operation of Relay 1 and Relay 2.

Disconnecting the diode between 17 and 18 will disable operation of Relay 1 from

overcurrent.

Latching output relays can be reset or disabled by bridging terminals 5 and 6.

Rev: 4-A-050213

Advertising