Littelfuse T2400 Series User Manual

T2400 series, Protection relays & controls, Generator & single-function protection–overcurrent

Advertising
background image

Protection Relays & Controls

© 2013 Littelfuse Protection Relays & Controls

Littelfuse.com/t2400

Generator & Single-Function Protection–Overcurrent

T2400 SerieS

3-Phase Dual Overcurrent Relay

Description

The T2400 3-Phase Dual Overcurrent Relay includes two

combined overcurrent relays, designed for protection or

monitoring of generators and power transmissions. A typical

application is to use one of the overcurrent functions to trip the

generator circuit breaker, and the other overcurrent function to

trip a non-essential consumer.
The T2400 consists of two overcurrent circuits with similar

current settings and time delays. Each circuit detects the

highest of the 3 input currents and, if this exceeds the preset

level (0.5-1.4 x I

N

), the corresponding pick-up LED will indicate

and the delay timer will be started. After the preset time

(3-30 sec.) has expired, the corresponding output relay and

LED will be activated, provided that the current level was

exceeded for the entire delay time.

Specifications

Trip Level

0.5-1.4 x I

N

Delay

3-30 sec.

Max. Voltage

660 V

Voltage Range

60-110%

Consumption

Voltage 5 VA at U

N

Current 0.3 VA at I

N

Continuous Current

2 x I

N

Frequency Range

45-400 Hz

Output Relay

Normally de-energized

Contact Rating

AC: 400 V, 5 A, 2000 VA; DC: 150 V, 5 A, 150 W

Overall Accuracy

±5%

Repeatability

±1%

Operating Temperature –20°C to + 70°C

Dielectric Test

2500 V, 50 Hz

EMC

CE according to EN50081-1, EN50082-1,

EN50081-2, EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate. Flame retardant

Weight

0.5 kg

Dimensions H

70 mm (2.76”); W 100 mm (3.94”);

D 115 mm (4.52”)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

OrderinG

number

TerminalS

i

n

FuncTiOn

1-3

2-3

T2400.0010 230 V

5 A

T2400.0020 450 V

400 V 5 A

T2400.0030 110 V

100 V 5 A

T2400.0040 450 V

400 V 5 A Latching output on relay 1,

6-60 sec. delay on relay 1

T2400.0050 480 V

415 V 5 A

T2400.0060 450 V

400 V 1 A

T2400.0070 450 V

400 V 5 A Latching output on relay 1,

normally energized relay 1

T2400.0080 127 V

120 V 5 A

T2400.0090 24 Vdc

5 A

Ordering Information

Simplified Circuit Diagram

Features & Benefits

Latching output relays are reset by disconnecting the power supply.
Other supply voltages and combinations are available on request.

I. OVERCURRENT

II. OVERCURRENT

I

1

U

I

2

I

3

2

11

12
13

14
15

16

1

3

10

9
8
7

6
5
4

L

1

L

2

L

3

SUPPLY

T2400

(3-Phase Dual

Overcurrent Relay)

FeaTureS

beneFiTS

Accepts high supply

voltage variation

Ensures correct operation in spite of voltage

supply fluctuations (fulfills marine class

requirement)

Visual indication of

power, pick-up, and

output trip

Provides quick and concise status information

Direct line-line or line-

neutral voltage supply

(up to 690 Vac)

Simplifies design and installation.

No need for PTs.

Combining 2 relays in

same enclosure

Economic solution for non-essential load

tripping, and occupying less space in the

switch panel

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN-rail or screw-mount

& adjustment by

potentiometers

Easy installation

Rev: 4-A-050213

Advertising