SE-105, SE-107 SEriES

Ground-Fault Ground-Check Monitor

Description

The SE-105/SE-107 is a combination ground-wire monitor

and ground-fault relay for resistance-grounded systems. It

continuously monitors the integrity of the ground conductor

to protect portable equipment from hazardous voltages

caused by ground faults. The SE-105/SE-107 is an excellent

choice for trailing cables 5 kV and under in underground mining

applications. For higher voltages or long-cable applications, see

the SE-134C/SE-135.

Specifications

IEEE Device Numbers

Checking or Interlocking Relay (3GC),

Ground Fault (50G/N, 51G/N)

Input Voltage

See ordering information

Dimensions

H 150 mm (5.9”); W 109 mm (4.3”);

D 100 mm (4.0”)

Trip Level Settings

0.5, 2.0, 4.0 A

Trip Time Settings

0.1-1.0 s

Contact Operating Mode

Selectable fail-safe or non-fail-safe (SE-105)

Fail-safe only (SE-107)

Harmonic Filtering

Standard feature

Reset Button

Local and remote

Output Contacts

Isolated Form A

Approvals

CSA certified,

UL Listed (E340889)

,

C-Tick (Australian)

Conformally Coated

Standard feature

Warranty

5 years

Mounting Surface

OrdEring numbEr

COntrOl pOwEr

SE-105

120 Vac

SE-105D

120 Vac/Vdc

SE-105E

240 Vac

SE-107

120 Vac

SE-107D

120 Vac/Vdc

SE-107E

240 Vac

Ordering Information

Consult manual online for additional ordering options.

Simplified Circuit Diagram

CT200 Series Current Transformer

Required CT detects ground-fault current.

1N5339B Termination Device

5 W axial-lead ground-check termination

; included

with SE-105/SE-107.

SE-TA6 Termination Assembly

Optional termination assembly with convenient

terminals and mounting holes

SE-TA6-SM Stud-Mount Termination Assembly

Optional 50 W ground-check termination that is

robust and compact for submersible pumps. Wire

lead simplifies installation.

Accessories

A

B

TRAILING

CABLE

CT

L2

L1

TERMINATION
DEVICE

A

G

GC

C

B

GROUNDED

SUPPLY

M

SE-105 SERIES

SE-107 SERIES

(Ground-Fault

Ground-Check

Monitor)

B

FEaturES

bEnEFitS

Adjustable pickup

(0.5, 2.0, 4.0 A)

Unit can be used on a wide variety of trailing

cable applications

Adjustable time delay

(0.1 - 2.0 s)

Adjustable trip delay for quick protection and

system coordination

Harmonic filter

Prevents false operation

Zener-characteristic

termination assembly

Provides reliable ground-check loop verification

Fail-safe ground-check circuit

Ensures ground-check circuit remains safe

even in the event of equipment failure

Conformal coating

Additional coating protects circuit boards

against harsh environment

SE-105: Selectable UV- or

shunt-trip mode

Provides flexibility for different applications

SE-107: UV-trip mode only

Eliminates chance of unauthorized change to

trip circuit

Features & Benefits

aCCESSOriES

rEquirEmEnt

CT200 Series

Required

1N5339B

Included

SE-TA6, SE-TA6-SM

Optional

SE-TA6A Series

Optional

RK-102, RK-105, RK-105I

Optional

RK-13

Optional

PPI-600V

Optional

A

trailing Cable protection–ground-Fault ground-Check monitoring

Littelfuse.com/se-105, Littelfuse.com/se-107

Rev: 4-A-050213

SE-105 Based on Manual Rev 12

SE-107 Based on Manual Rev 4