Littelfuse M8100 Series User Manual

M8100 series, Generator control, Basic

Advertising
background image

Generator Control

© 2013 Littelfuse Protection Relays & Controls

Basic

M8100 SerieS

Synchroscope

Description

The M8100 Synchroscope provides illuminated indication of

the phase and frequency difference between voltages on

two separate AC systems, e.g. a generator and a busbar. The

M8100 will also indicate whether or not the two systems are

on voltage.
The M8100 is also available in a version with a built-in relay

for automatic closure of the circuit breaker (Synchro Check

Relay). The voltage and frequency are adjusted by the

operator to roughly match the values required, and the unit

will provide a closing signal to the circuit breaker at phase

accordance.

Ordering Information

Simplified Circuit Diagram

FeatureS

BeNeFitS

High resolution visual

indication by 38 LEDs

Phase and frequency difference; Bus and

generator voltage and phase accordance.

Provides quick, concise status information;

steady viewing of the synchronization process.

Available with check

synchronizer relay

Enables use as manual synchronizing unit, or as

auto-synchronizer back-up

Versions available with

dead bus closure

Enables use as dead bus monitor in back-up

power installation

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

Sturdy casing for flush-

mount installation, Q96

standard, with protection

class IP52 on the front

Easy installation, allowing use in harsh

environments

Features & Benefits

www.littelfuse.com/m8100

BUS.

GEN.

G

1
2
3

4
5
6

L

1

L

2

L

3

M8100

(Synchroscope)

With Check Synchronizer

Without Check Synchronizer

BUS.

DEAD BUS

ENABLE

CLOSING

SIGNAL

GEN.

G

1
2
3

7

8

4

9

10

5
6

L

1

L

2

L

3

M8100

(Synchroscope)

Other voltages are available on request.

OrderiNg

NuMBer

terMiNalS

FuNctiON

1-1

5-7

1-3

6-7

M8100.0010

450 V

400 V

M8100.0020

230 V

M8100.0030

480 V

415 V

M8100.0040

110 V

100 V

M8100.0050

450 V

400 V

With check synchronizer relay

M8100.0060

230 V

With check synchronizer relay

M8100.0070

480 V

415 V

With check synchronizer relay

M8100.0080

110 V

100 V

With check synchronizer relay

Specifications

Max. Voltage

660 V

Voltage Range

70-110%

Consumption

2 x 3 VA max.

Frequency Range

35-70 Hz

Pull-in/Drop-out

Diff. Frequency

±9 Hz

Operating Temperature –20°C to +70°C

EMC

CE according to EN50081-1, EN50082-1,

EN50081-2, EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Flame retardant

Weight

0.7 kg

Dimensions

H 96 mm (3.8“); W 96 mm (3.8“); D 80 mm (3.1“)

Panel Cut-out

H 92 mm (3.6“); W 92 mm (3.6“)

Unit with check synchronizer relay

Voltage Difference

10-20%

Frequency Difference 0.15-0.3 Hz Combined setting

Phase Difference

6-12°

Dead-bus Delay

1s-5s

Dead-bus Voltage Offset 20%-40%

Min. Generator Voltage

for DB Closure

80% of nominal voltage

Contact Rating

AC: 250 V, 1.2 V, 125 VA; DC: 30 V, 1 A, 30 W

}

Rev: 4-A-050313