Generator Control

© 2013 Littelfuse Protection Relays & Controls

Basic Generator Protection

T5000 SerieS

Paralleling Relay

Description

The T5000 Paralleling Relay is a check synchronizer, inhibiting

closure of circuit breaker if synchronizing parameters such as

voltage, frequency and phase angle are outside limits, thus

preventing generator damage and disturbance to the busbar.
The T5000 can also be used as synchronizing aid for manual

or automatic synchronization where voltage and frequency

are adjusted by the operator to roughly the values required,

and the unit will provide a closing signal to the circuit breaker

at phase accordance.
Automatic closure

In order to use the T5000 with automatic closure, terminals

19 and 20 should be interconnected, and the T5000 will now

operate as illustrated in graph at left.
Line I shows the closing signal directly from the T5000.
Line II shows the main contact closure with an additional

circuit breaker operation time of 50 msec.

Ordering Information

Simplified Circuit Diagram

FeaTureS

BeNeFiTS

Visual indication of

voltage and closing signal Provides quick and concise status information
Adjustable combined

setting, %U, of

synchronizing window

(delta frequency, delta voltage,

delta phase)

Facilitates adjustment during installation and

commissioning

Automatic

closure function

Enables use with fast reacting circuit breakers

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN rail or screw-mount

Easy installation

N-G continuity alarm

Monitors neutral-to-ground integrity and alarms

if ground path becomes open circuit

Passive filtering

Eliminates nuisance tripping

Features & Benefits

www.littelfuse.com/t5000

Other supply voltages, nominal currents and combinations are available on request.

OrderiNG

NumBer

TermiNalS

FuNcTiON

1-1

5-7

1-3

6-7

T5000.0010 450 V 400 V
T5000.0020 230 V
T5000.0030 480 V 415 V
T5000.0040 110 V 100 V
T5000.0050 127 V 120 V
T5000.0060 480 V 415 V Df=9-13.5°, DF=0.2-0.3 Hz
T5000.0070 450 V 400 V DU=15-20%, Df=9-13.5°, DF=0.2-0.3 Hz
T5000.0080 110 V 100 V DU=15-20%, Df=9-13.5°, DF=0.2-0.3n Hz
T5000.0090 450 V 400 V Df=9-13.5°, DF=0.2-0.3 Hz
T5000.0100 660 V

CLOSING

SIGNAL

AUTOMATIC CLOSURE

19

9

20

10

7

6

5

2
3

1

L

1

L

2

L

3

T5000

(Paralleling Relay)

6
4
2
0
2
4
6

0.15 Hz

+ 50 msec.

Specifications

Max. Voltage

660 V

Voltage Range

70-110%

Consumption

2 x 5 VA max.

Frequency Range

45-65 Hz

Voltage Difference

10-15%

Frequency Difference 0.15 - 0.225 Hz Combined setting

Phase Difference

6-9°

Contact rating

AC: 400 V, 5 A, 1250 VA; DC: 150 V, 5 A, 120 W

Operating Temperature –20°C to +70°C

Dielectric Test

2500 V, 50 Hz

EMC

CE according to EN50081-1, EN50082-1,

EN50081-2, EN50082-2

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate, flame retardant

Weight

0.7 kg

Dimensions

H 70 mm (2.7“); W 100 mm (3.9“);

D 115 mm (4.5“)