Littelfuse T4800 Series User Manual

T4800 series, Generator control, Basic

Advertising
background image

Generator Control

© 2013 Littelfuse Protection Relays & Controls

Basic

T4800 SerieS

Load Sharer for Conventional Governors

Description

The T4800 Load Sharer provides automatic load sharing and

frequency control for parallel running generators. The load

sharing is proportional, meaning that the generators will be

loaded equally compared to their individual capacity.
The load on each generator is compared with the load on

the other generators and corrected until balance is obtained.

Load sharing is necessary after synchronization in order to

reestablish load balance and to obtain long term stability of

load and system frequency (compensating the droop of the

speed governor).
The T4800 has a built-in reverse power protection with

selectable limits and time delays.

Ordering Information

Simplified Circuit Diagram

FeaTureS

BeNeFiTS

Adjustable delta frequency,

stability and % load

deviation by front panel

potentiometers

Facilitates adjustment during installation and

commissioning. Load deviation adjustment

enables paralleling of differenst size

generators.

Inputs for disabling internal

frequency control

Enables operation where system frequency

is set externally such as in grid-parallel

operation

Reverse power trip

Economic solution for reverse power

protection

Visual indication of voltage,

increase/decrease and

unload signals

Provides quick and concise status

information

Direct line-line voltage

supply (up to 690 Vac)

Simplifies design and installation–no need for

PTs–or separate power supply

Galvanic isolated inputs

Protects the unit against high AC voltage and

currents from the installation including spikes

DIN rail or screw-mount

Easy installation

Features & Benefits

Other supply voltages, nominal currents and combinations are available on request.

Specifications

Max. Voltage

660 V

Voltage Range

70-110%

Consumption

Voltage 4 VA at U

N

; Current 0.4 VA at U

N

;

Continuous Current

2 x I

N

Frequency Range

35-70 Hz

Frequency Adjustment 48-62 Hz

Proportional Band

±50 - 250% load; ±5 - 25% frequency

Dead Band Zone

±2 - 10% load; ±0.2 - 1.0% frequency

Contact rating

AC: 400 V, 2 A, 250 VA

DC: 110 V, 2 A, 100 W

Operating Temperature –20°C to +70°C

Vibration Test

4 g RMS according to IEC 60068-2-64

EMC

CE according to EN50081-1, EN50082-1,

EN50081-2, EN50082-2, EN61000-6-2:1999

Approvals

Certified by major marine classification societies

Burn-in

50 hours before final test

Enclosure Material

Polycarbonate, flame retardant

Weight

0.7 kg

Dimensions

H 70 mm (2.7“); W 150 mm (5.9“);

D 115 mm (4.5“)

Installation

35 mm DIN rail or 4 mm (

3

/

16

”) screws

www.littelfuse.com/t4800

BUS

U

N

I

N

C/B

GEN

M

1

2

3

4

5

6

7

8

9

10

11

12

12

13

13

14

15

16

17 18

19

20 21

22 23 24

25

26

27

28

29

30

31 32

L

1

L

2

L

3

T4800

(Load Sharer)

UNLOAD

UNLOAD

SYNC. T4500

NEXT

T4800

COM.

PARALLEL

LINES

INCR. DECR.

REVERSE POWER

FREQ.

OUT

FREQ.

IN

FREQ.

IN

SYNC.

TRIP

AUTO

WATT

IN

TEST

OUT

+

OrderiNg

NumBer

TermiNalS

i

N

1-1

1-3

T4800.0010

450 V

400 V

5 A

T4800.0020

230 V

5 A

T4800.0030

480 V

415 V

5 A

T4800.0040

110 V

100 V

1 A

T4800.0050

450 V

400 V

1 A

T4800.0060

127 V

120 V

5 A

T4800.0070

110 V

100 V

5 A

Rev: 4-A-050313