Wiring diagram, Mounting hints – OSRAM Touch DIM PD LI 2P WOS User Manual

Page 2

Advertising
background image

Page 2

OSRAM - operating instructions: TOUCH DIM PD LI 2P WOS

Wiring diagram

Mounting hints

The sensor is connected to a 3 wire cable which is admitted for mains voltage. Parallel connection of
several sensors is not allowed. The sensor is typically installed in luminaires, ceiling installation is
possible by use of a flush device box and an adequate cover.

Following sensor heads are approved to be used with the Touch DIM PD LI 2P WOS sensor:
(-> sensor head not included in delivery)

PANASONIC NaPiOn sensors (passiv infrared)
Digital version


- Standard type Standard

anthracite

AMN11111

(5m range)

white

AMN11112

Economy

anthrazit AMN31111

white

AMN31112


- Type for small movements

Standard

anthracite

AMN12111

white

AMN12112

Economy

anthracite

AMN32111

white

AMN32112


- Spot type

Standard anthracite AMN13111

white

AMN13112

Economy

anthracite

AMN33111

white

AMN33112


- 10m type

Standard

anthracite

AMN14111

white

AMN14112

Economy

anthracite

AMN34111

white

AMN34112

When adding a sensor head to the sensor, please note the following:
• The entire workplace must lie within the monitoring cone of the sensor.

• The sensor must not be exposed to drafts (e.g. near air vents). A draft could be misinterpreted as

the presence of a person in the room.






ECG QTi DALI

Lamp

1

2

3

4

DA

DA

~

~

ECG QTi DALI

Lamp

1

2

3

4

DA

DA

~

~

N

PE

Push button

(manual

control)

L

TOUCH DIM

Sensor

ECG QTi DALI

Lamp

1

2

3

4

DA

DA

~

~

ECG QTi DALI

Lamp

1

2

3

4

DA

DA

~

~

max. 4

QTi ECG

or HTi

transform

ers

L N S

signal wire length max. 10m

Push button and sensor have to be
connected to the same mains phase!