GE Industrial Solutions GE TR7000 Series User Manual

Page 5

Advertising
background image

2020004602 (12/10) Page 5 of 17

 M

AXIMUM

C

ONTINUOUS

O

PERATING

V

OLTAGE

(MCOV)

This value defines the maximum line-to-line or line-to-neutral continuous AC voltage that can be

safely applied to the protector. MCOV levels for GE TR7000 Series SPDs are set at 115% of nominal

system voltage. For 120-volt AC systems, the MCOV is 125%. If there is a risk that the electrical

system voltage could exceed MCOV, or if any unusually high power frequencies, Temporary Over

Voltages (TOV), or phase swells are anticipated, contact your GE Sales Engineer for further

assistance.

 E

LECTRICAL

S

YSTEM

C

ONFIGURATION

Protectors are available for single (split) phase with neutral and ground, three-phase grounded WYE,

three-phase ungrounded WYE, three-phase high-leg delta, and for three-phase ungrounded delta

systems. (See page 7 for power source configurations)

 P

EAK

I

MPULSE

R

ATING

Peak surge current capability is an important characteristic for a SPD. The rating per mode should

equal or exceed the maximum surge expected in service. GE TR7000 wall mount SPDs are available

in maximum surge ratings of 65kA, 80kA, 100kA, 125kA, 150kA, 200kA and 300kA.

 UL 1449 N

OMINAL

D

ISCHARGE CURRENT

(In)

The UL Nominal Discharge Current (In) rating should be considered when an SPD is selected for use

within a UL96A Lightning Protection System. UL96A requires a Nominal Discharge Current (In)

rating of 20kA for Type 1 or Type 2 SPDs.

 S

HORT

C

IRCUIT

C

URRENT

R

ATING

GE TR7000 Wall Mounted SPD units are UL certified for use on electrical systems with rated

ampacities up to 200,000 symmetrical amperes when installed behind a circuit breaker rated 60A.

 E

NVIRONMENTAL

R

ATINGS

NEMA Ratings of 1, 4, 4x, and 12 are available. Please refer to the model number suffix to verify the

correct enclosure for the application. The SPD is designed to operate within an ambient

temperature range of –40C (-40F) to +65C (+149F) with a relative humidity level between 0-95%

non-condensing.



A direct lightning strike, that occurs within close proximity of an installed SPD, can result in

surge currents that exceed the SPD’s energy handling capability. This can result in reduced

life expectancy or pre-mature failure of the SPD. Electrical power system supply voltages in

excess of the SPD MCOV rating, can also cause SPD failure.



Should a condition occur that results in premature failure of the SPD, the suppression

circuitry will short, allowing the integral fusing to interrupt current flow through the SPD

without disrupting power to the protected equipment. In the event of limited available fault

currents, the 60A breaker will operate to remove the SPD. Fault currents of less than 60A will

be interrupted by the integral thermal fusing. In each case the SPD will be removed from the

power system and the load equipment will remain unprotected from subsequent surge

activity until the SPD is replaced.



Increased rate of rise or higher surge current magnitudes can result in increased surge let-

thru levels due to the non-linear clamping characteristics of SPDs. Conditions can occur

where the surge withstand capability of the protected equipment is exceeded even though

the SPD is functioning properly. In such cases, additional SPDs may be required, located

closer to the sensitive load(s). (For additional information, refer to Standard IEEE 1100-2005,

Section 3.4.3)



GE TR7000 Series WYE-connected units have both normal mode (L-N, L-L) and common

mode (L-G, N-G) protection. Protection between neutral and ground is provided on units

designed for WYE-connected applications.

Advertising