3. Install the breaker module.

Fully retract the latches

and hook one side of the breaker module to the
interior rail, as shown in Figure 4. Release the latch.
Pivot the module onto the bus bars and engage the
second latch. Release the latch. Tighten the latch
screws to 25 in-lb, as shown in Figure 5.

Figure 4. Positioning the breaker module on the interior rail.

Figure 5. Securing the module to the interior.

4. Wire the circuits.

Refer to the label on the circuit

breaker for the proper tightening torque.

5. Filler plate kits.

Install filler plate kit AFP4SGS on the

module.

Attention – Procedure for Aluminum
Terminations

1.

Strip the insulation, being careful to not nick the wire.

2.

Clean the wire strands with a wire brush.

3.

Thoroughly coat the stripped conductor with a
suitable antioxidant compound, such as ALNOX or
PENETROX A13.

4.

Insert the conductor and tighten the connector screw
to the torque indicated on the rating label.

g

GE Industrial Systems

General Electric Company
41 Woodford Ave., Plainville, CT 06062

GEH5674 R03 0701

© 2001 General Electric Company

These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that
may be met in connection with installation, operation, or maintenance. Should further information be desired or should
particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the
GE Company.