Data sheet, Input; default outputs: ±54v, Absolute maximum ratings – GE Industrial Solutions CP2000AC54TE User Manual

Page 2: Electrical specifications

Advertising
background image

GE

Data Sheet

CP2000AC54TE CPL High Efficiency Rectifier

100-120/200-277V

AC

input; Default Outputs: ±54V

DC

@ 2000W, 5V

DC

@ 4W

August 16, 2013

©2013 General Electric Company. All rights reserved.

Page 2

Absolute Maximum Ratings

Stresses in excess of the absolute maximum ratings can cause permanent damage to the device. These are absolute stress ratings

only, functional operation of the device is not implied at these or any other conditions in excess of those given in the operations
sections of the data sheet. Exposure to absolute maximum ratings for extended periods can adversely affect the device reliability.

Parameter

Symbol

Min

Max

Unit

Input Voltage: Continuous

VIN

0

300

V

AC

Operating Ambient Temperature

TA

-10

75

1

°C

Storage Temperature

Tstg

-40

85

°C

I/O Isolation voltage to Frame (100% factory Hi-Pot tested)

1500

V

AC

Electrical Specifications

Unless otherwise indicated, specifications apply over all operating input voltage, Vo=54V

DC

, resistive load, and temperature

conditions.

INPUT

Parameter

Symbol

Min

Typ

Max

Unit

Startup Input Voltage
Low-line Operation
High-line Operation

V

IN



90

185

V

AC

Operating Voltage Range
Low-line Configuration
High-line Configuration

V

IN

90

185

100 – 120

200 - 277

140
300

V

AC

Input Voltage Swell (no damage)

305

Input Frequency

F

IN

47 66

Hz

Input Current; at 110V

AC

at 240V

AC

I

IN

11.9
13.1

A

AC

Inrush Transient (at 25°C, excluding X-Capacitor charging)

I

IN

25 30

A

PK

Idle Power (at 220V

AC

) 54V OFF

54V ON @ Io=0

P

IN

8.2

16

W

Input Leakage Current (265V

AC

, 60Hz)

I

IN

2.5 3.5

mA

Power Factor (50 – 100% load)

PF

0.96 0.995

Efficiency

2

(30 – 80% of FL, 240V

AC

@ 25C)

94.5 96.2

%

Holdup time (output allowed to decay down to 40V

DC

)

For loads below 1200W

T

20
30

ms

Ride thru (tested at 115V @ 230V. (Complies to CISPR24)

T

1/2

1

cycle

Power Fail Warning

3

(main output allowed to decay to 40V

DC

)

PFW 3

5

ms

Isolation (per EN60950) (

consult factory for testing to this requirement)

Input-Chassis/Signals
Input - Output

V

1500
3000

V

AC

V

AC

1

Derated above 50C at 2.5%/C

2

See efficiency curve in the Characteristics Curves section.

3

Internal protection circuits may override the PFW signal and may trigger an immediate shutdown.

Advertising