DEH44151 Installation Instructions

Neutral mounting kit

1

Catalog number – TNK400

Introduction

This bulletin provides instructions for

installing Neutral lug kit – TNK400 on all

GE Double throw safety switch rated

400A.

WARNING: Hazard of electrical shock or

burn. Turn off power before working

inside this equipment.

Description

This neutral kit consists of the following

parts:

1. One (1) Neutral assembly

2. Two (2) 1/4-20 X 9/16” mounting

screws

Mounting Instruction

1. Tighten item 2 (Mounting screws) in to

mounting hole in the enclosure. Ref. Fig 1

2. For bonding, bare wire 1/0 CU/AL is to

be used to connect small lug in neutral

assembly to ground kit (Order

separately).

Wire range: 2 – 600MCM CU/AL

Fig 1


g

These instructions do not purport to cover all details or variations in equipment nor to provide

for every possible contingency to be met in connection with installation operation or

maintenance. Should further information be desired or should particular problems arise which

are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the GE

Company.

General Electric Company

41 Woodford Ave., Plainville, CT. 06062

GE Consumer & Industrial

DEH44151 R01 08/07 © 2007 General Electric