Figure 5 and figure 6, measure the, Turns), as illustrated in figure 6, Step 3 – install the circuit breaker – GE Industrial Solutions Record Plus Variable Depth Operating Mechanism: FE250 User Manual

Page 3

Advertising
background image

8. With the handle and mechanism in the

OFF

position,

place the small hole in the other end of the drive rod

[4] over the stud in the handle drive link.

9. Slide the drive pin [5] through the holes in the

handle drive link and the end of the drive rod [4].

Place a flat washer [6] over the end of the pin, then

slide the cotter pin [7] through the hole in the drive

pin [5], as illustrated in Figure 6. Do not bend the

cotter pin at this time, since slight movement of the

handle may be necessary to align the pin and hole.

Figure 5. Side view of enclosure, showing dimension D.

Figure 6. Installing the drive rod.

Step 3 – Install the Circuit

Breaker

This procedure is illustrated in Figure 7.

1. Move the STDA handle to the

ON

position. Be

careful to keep your hands away from the operating

mechanism while performing this installation.

2. Turn the circuit breaker to the

ON

position.

3. Install the circuit breaker on the operating

mechanism by inserting the four #8-32

x

2

7

/

8

" screws

[8] and lock washers [9] into the mounting holes in

the breaker and into the corresponding tapped holes

in the mechanism, as illustrated in Figure 7.

4. Place the yoke top plate [10] on the left and right

yoke plates with the breaker handle fitting through

the cutout in the top plate. Secure with four #8-32

x

1

/

4

" screws [11] and lock washers [9] into the tapped

holes in the yoke side plates.

5. Attempt to turn the breaker

OFF

with the STDA

handle. If the breaker does not move to the

OFF

position, disconnect the drive rod [4] from the

handle and thread the rod one turn further

(clockwise) into the drive stud. Reattach the drive

rod to the handle mechanism. Repeat until the

breaker turns

OFF

with the handle mechanism.

6. Attempt to turn the breaker

ON

with the handle

mechanism. If the breaker does not turn

ON

, repeat

the adjustment of step 5 until moving the handle

ON

also turns the breaker

ON

.

7. With the breaker in the

ON

position, use the TRIP

button to open the breaker. Attempt to reset the

breaker by moving the handle to the

OFF

(reset)

position. If the breaker is

RESET

, it can be turned

ON

and

OFF

. If the breaker will not reset, repeat the

adjustment of step 5 until the breaker resets.

8. When the

ON

,

OFF

, and

RESET

positions are working

properly with the handle mechanism, bend the legs

of the cotter pin [7] to secure the drive rod [4] in

place.

9. Attach the handle bias spring, illustrated in Figure 6,

included with the STDA handle mechanism kit.

10. Tighten all #8-32 screws to 20–25 in-lb and

1

/

4

-20

screws to 45–50 in-lb.

11. Complete the circuit breaker installation according

to DEH40463, the installation instructions supplied

with the breaker.

Advertising