Flat front Terminations
Envelope 3 (Up to 6400A)

Terminal assemblies are supplied with the
Entelliguard breaker.














Fig B. Heat Sink Assembly

Catalogue No:




EntelliGuard

®

G

Circuit Breaker

Accessories



Flat Front Terminations for Fixed
Breaker



WARNING: Before installing any accessories, turn the

breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.







Flat Front Terminations Assembly Procedure:

1. Turn the breaker off and discharge the closing

springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background.


2. Assemble the Flat Front to the rear terminals with

M12 Hardware as shown in Fig A., Tighten the
hardware to torque 50N-m (36.9 ft-lbs)

3. Assemble the Heat Sink with M8 Hardware to Flat

Front as shown in Fig B. Tighten to torque 12-
14N-m (8.9-10.3 ft-lbs)


4. Similarly populate the Flat Front and Heat sink on

all other terminals as shown in fig B & C.

5. The bus bars to be supported within 200mm

distance and tightened to 50Nm (36.9 ft-lbs)
torque.

Catalog #

Description

GBB3TBF3 Envelope

3-3pole 4000-6000A

GBB3TBF4 Envelope 3-4pole 4000-6000A

AVERTISSEMENT: Avant d’installer tout accessoire,

mettre le disjoncteur en position OFF, le déconnecter
de toute tension d’alimentation, et décharger les

resorts d’armement

DEH-41463 Installation Instructions