GE Industrial Solutions Voltage Conditioner SVCAA User Manual

Voltage conditioner assembly, Geh-6254 installation instructions, Ge energy industrial solutions

Advertising
background image

Overview
The General Electric Voltage Conditioner Assembly
is used to provide voltage-sensing signals to
Spectra

®

RMS Molded-Case Circuit Breakers with

microEntelliGuard

TM

or MicroVersaTrip

®

PM/Plus Trip

Units via the Distribution Cable System.

The assembly has the maximum capacity to provide
voltage signals to a Distribution Cable System
consisting of 20 Spectra

®

RMS Molded-Case Circuit

Breakers with microEntelliGuard

TM

or MicroVersaTrip

®

PM/Plus Trip Units with a maximum system cable
length of 40 feet.

The Voltage Conditioner Assembly requires a power
supply source voltage of +24Vdc to operate properly.
The Power Supply Assembly (catalog number SPSAA)
or Power Supply Plate (catalog number SPSAI20,
SPSA208, SPSA240, SPSA480 or SPSA600) can provide
this required input. The unit also requires 120Vac @60
Hz voltage inputs from the secondary of three 1-VA
high accuracy potential transformers (not included).
The primary side of each potential transformer must
be fused with 2-amp class CC fuses (not included). The
Voltage Conditioner Assembly is designed to operate in
temperatures between 0°C and 70°C.

GEH-6254 Installation Instructions

Voltage Conditioner Assembly

For Spectra

®

RMS Molded-Case Circuit Breakers

with microEntelliGuard

TM

, MicroVersaTrip

®

PM or MicroVersaTrip

®

Plus Trip Units

For Catalog Number SVCAA

Circuit Breaker Accessory

GE Energy

Industrial Solutions

Advertising