Trouble-shooting – GE Industrial Solutions Power Break II Bell Alarm with Lockout User Manual

Page 4

Advertising
background image

Trouble-Shooting

The following guide is provided for trouble-shooting and
isolating common problems. It does not cover every possible
situation. Contact the ED&C Customer Support Center at 800-
843-3742 if any problem is not resolved by these procedures.

Symptom

Possible Cause

Corrective Action

1.

The circuit breaker will
not turn on.

The Bell Alarm with Lockout is
not reset.

Push firmly on the reset button on the front of the Bell
Alarm with Lockout module until it latches.

2.

The lockout function is not
activated on a trip, the
outputs do not change
state on a trip, or the
normally closed terminals
show no continuity.

The module is not fully seated in
the compartment.

The Bell Alarm with Lockout
configuration switches on the rear
of the MicroVersaTrip Plus or
MicroVersaTrip PM Trip Unit
are not properly set.

Push the Bell Alarm with Lockout module firmly into the
compartment and tighten the hold-down screw to 9 in-lbs.
Follow the procedure to remove the Trip Unit and set the
switches. Check that the switches have been set correctly.

These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency
that may be met in connection with installation, operation, or maintenance. Should further information be desired or
should particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be
referred to the GE Company.