GE

CAR1248TN series rectifier

Input: 90Vac to 264Vac; Output: -54Vdc @ 1200W

November 20, 2012

©2012 General Electric Company. All rights reserved.

Page 3

-54V

dc

MAIN OUTPUT (continued)

Parameter

Device

Symbol

Min

Typ

Max

Unit

Turn-ON delay

All

T

2

sec

Remote ON/OFF delay time

40

ms

Turn-ON rise time (10 – 90% of V

out

)

50

ms

Transient response 50% step [10%-60%, 50% - 100%]

(dI/dt – 1A/µs, recovery 300µs)

V

out

-5 +5

%V

out

Programmable range (hardware & software)

-42

-58

V

dc

Overvoltage protection, latched

(reset by cycling OFF/ON via hardware or software)

I

out

-58 -59 -60 V

dc

Output current V

in

– high line

V

in

– low line

0

22.2
18.5

A

dc

Power/Current limit V

in

– high line

V

in

– low line

P

out

1200
1000

W

Power limit down to -48Vdc

Current limit below -48Vdc, Hiccup (programmable level)

I

out

113 130

% of FL

Active current share

I

out

-10 +10

%

of

FL

Environmental, Reliability

Parameter

Min

Typ

Max

Units

Notes

Ambient Temperature
Operating
Altitude Operating
Power Derating

-10

3

50

2250

2.5

°C

m

%/°C


Air inlet from sea level to 5,000 feet.
7400 ft
51°C to 70C

Storage
Altitude non-operating

-40

85

8200

°C

m


30,000 ft

Over Temperature Protection

120 / 110

°C

Shutdown / Restart

Humidity Operating

Storage

30
10

95

95

%

Relative humidity, non-condensing

Shock and Vibration acceleration

6

Grms

NEBS GR-63-CORE, Level 3, 20 -2000Hz, minimum 30
minutes

Earthquake Rating

4

Zone

NEBS GR-63-CORE, all floors, Seismic Zone 4 Designed and

tested to meet NEBS specifications.

MTBF

100,000
200,000

Hrs

Full load, 50C ambient, per Bellcore RPP
Demonstrated


3

The unit will start up at -40C but is not guaranteed to meet specification limits until it is within the operating ambient range.