6. Assemble remaining terminal assemblies similarly

on all poles so as to populate as 3pole / 4 pole
breaker fig C & D.


7. The bus bars to be supported within 200mm

distance and tightened to 80Nm (59 ft-lbs) torque
































Fig C, Envelope 2 , 3000A UL 3 Pole

Heat Sink LH

(with clearance hole)

Heat Sink RH

(with tapping)

M6 Hardware
8Nm torque

Heat Sink LH

(with clearance hole)

Heat Sink RH

(with tapping)

M6 Hardware
8Nm torque

Fig D, Envelope 2 , 3000A UL 4 Pole

Fig B. Heat sink assembly to terminal assembly for 3000

Amperes (UL)

These instructions do not purport to cover all details or variations in equipment nor, to provide contingency to be met in connection
with installation, operation, or maintenance. Should further information be desired, or should particular problems arise which are not

covered sufficiently for the purchaser’s purposes, the matter should be referred to GE.