DEH40151

DEH40151 Rev.No.02

4

Figure 3. Removing the shield inserts from the shield for SF breaker installation in

A –Series

®

II Panelboards.


11. To install branch breaker (kit ASPP6SF3S) on left side of interior, place the filler

plate [11] over the dead front so that the four same-size holes line up with the
threaded holes of the dead front, as illustrated in Figure 4. Fasten filler plate to the
dead front with four #10-32 x

3

/

8

screws [12] tightened to 27-36 in-lb.

12. To install branch breaker (kit ASPP6SF3S) on right side of interior, flip filler

plate [11] and place it over the dead front so that the four same-size holes line up
with the threaded holes of the dead front, as similar to step 11. Fasten filler plate
to the dead front with four #10-32 x

3

/

8

screws [12] tightened to 27-36 in-lb.

13. Reattach the dead front to the interior with the 8 screws removed in step 2.

Tighten the screws to 27-36 in-lb.