GE Industrial Solutions Spectra Series Power Panelboards Bolt-On Main Lug Kits User Manual

Page 2

Advertising
background image

3. Align the mounting holes.

Align the lug strap

mounting holes with the first and third bus holes from
the box end stamped

LINE

on the rear row of holes, as

shown in Figure 4.

Figure 4. Bus bar mounting holes.

4. Fasten the lug straps to the bus

using a carriage bolt,

flat washer, Belleville washer, and nut, as shown in
Figures 2 and 3. Tighten these bolted connections to
200–250 in.-lb.

5. Install the wire barriers.

Position the wire barriers so

that the second and fourth holes from the top of the
wire barrier align with the first and fourth holes of the
panel side rails or Z rails, as shown in Figure 5. Secure
the wire barriers to the panel side rails or Z rails using
the thread-forming screws supplied.

Figure 5. Wire barrier installation.

6. Wire the lugs

using the conductor sizes and tightening

torques listed in Table 1. If compression lugs are used,
follow the tool and wire information stamped on the
lugs.

Lug Part No.

Torque,

in.-lb.

Wire Size

(# of wires)

252B3638G9–10

375

8–500 kcmil (1)

#2/0–600 kcmil (1)

252B3638G1–2

450

2/0–600 kcmil (4)

252B3638G3–8

450

2/0–600 kcmil (8)

GEA2-750

475

3/0–750 kcmil (2)

Table 1. Recommended tightening torque and wire sizes.

7. Install the cover.

Lug kits whose catalog numbers have

an F suffix include cover plates. Two covers are
included: one for 36"- and 40"-wide boxes and one for
44"-wide boxes. Choose the appropriate cover for the
box to be used.
Attach the cover to the barriers in four places with the
screws and nut fasteners provided, as shown in Figures
6 and 7. Also use the black spacers for the style of
cover shown in Figure 7. Tighten the screws to 25–30
in.-lb.

Figure 6. Installing the cover.

Mounting Holes

Wire

Barrier

Panel Side

Rail

Thread-

Forming

Screws

Cover

Screw

Nut

Fastener

Barrier

Advertising