Replacing fuse, Breaker envelope frame size chart, Mounting tube accessory for oem breaker cassette – GE Industrial Solutions Remote Racking Operator: Low Voltage EntelliGuard G Circuit Breakers User Manual

Page 5

Advertising
background image

5

Breaker Envelope Frame Size Chart


In the catalog number printed on the breaker label, the 5

th

digit is identified as the breaker type and can

be found in the first column in the table below. Determine the envelope frame size by looking up the
breaker type and finding the Amp rating. The chart will show which envelope the breaker falls under.

Interrupting Rating Tier ANSI/UL1066 Devices, LVPCB

Frame 1

Frame 2

Frame 3

Type

240 V

480 V

600 V

1/2S Withstand

400 to 2000

3200

400 to 3200

3200

4000 to 5000

N 65,000 65,000 65,000

65,000

X

X

H 85,000 85,000 65,000

85,000

X

E 85,000 85,000 85,000

85,000

X

M 100,000 100,000 85,000

85,000

X

X

B 100,000

100,000 100,000

100,000

X X

L 150,000

150,000 100,000

100,000

X X

Mounting Tube Accessory For OEM Breaker
Cassette

Part number 0275B8280G001

The OEM cassette is equipped with a black plastic

racking handle storage tube. If you have an OEM
cassette the plastic part needs to be removed and
this part needs to be installed. To identify an OEM
breaker, the sixth character in the 20-digit catalog

number will be 1, 2 or 3 if it is an OEM breaker. If the
sixth digit is a D, then it is an AKD-20 cassette.
Hardware for mounting the metal tube is already in
the cassette. The nut needs to be loosened, slide in
the tube from the side and retighten the nut to 25 lb-

in. See figures 6 and 7

Fig 6. Installing the mounting tube

Fig 7. Mounting Tube Assembly. Part No.
0275B8280G001

Section 4.3

Replacing Fuse

Fig 8. Enclosure Fuse Holder

The enclosed drive is protected by an accessible
fuse as shown in figure 8. To replace the fuse,
turn the fuse holder cap counter-clockwise and

remove the 8A 250 volt fuse and replace with a
fuse of the same size and rating.

Advertising