GE Industrial Solutions SDCJBB User Manual

Distribution cable junction box, Deh-006 installation instructions, Ge energy industrial solutions

Advertising
background image

Overview
The General Electric Distribution Cable Junction Box
is a modular connector used to provide quick, easy
and reliable attachment of Spectra

®

RMS Molded-

Case Circuit Breakers with microEntelliGuard

TM

,

MicroVersaTrip

®

PM or Plus Trip Units to the Distribution

Cable System. The electronic signals supported by the
Distribution Cable Junction Box vary depending on
the type of Molded-Case Circuit Breaker used; a list of
supported functions appears below.

Input signals to Spectra

®

RMS Breaker with

MicroVersaTrip

®

PM Trip Unit

• control power (+24vdc)
• control power (common)
• system communications (Comm +)
• system communications (Comm –)
• breaker position (via installed aux. switch - red wire)
• breaker position (via installed aux. switch - white wire)
• voltage A f (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• voltage B f (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• voltage C f (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• neutral current sensor - black (for equipment ground

fault)

1

• neutral current sensor - white (for equipment ground

fault)

1

Input signals to Spectra

®

RMS Breaker with

MicroVersaTrip

®

Plus Trip Unit

• control power (+24vdc)
• control power (common)
• neutral current sensor - black (for equipment ground

fault)

1

• neutral current sensor - white (for equipment ground

fault)

1

Input signals to Spectra

®

RMS Breaker with

microEntelliGuard

Trip Unit

• control power (+24vdc)
• control power (common)
• system communications (Comm +)
• system communications (Comm –)
• breaker position (via installed aux. switch - red wire)
• breaker position (via installed aux. switch - white wire)
• voltage A f (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• voltage B f (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• voltage C f (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• neutral current sensor - black (for equipment ground

fault)

1

• neutral current sensor - white (for equipment ground

fault)

1

DEH-006 Installation Instructions

Distribution Cable Junction Box

For Spectra

®

RMS Molded-Case Circuit Breakers with microEntelliGuard

TM

Trip Units,

MicroVersaTrip

®

PM Trip Units or MicroVersaTrip

®

Plus Trip Units

For Catalog Number SDCJBB

Circuit Breaker Accessory

GE Energy

Industrial Solutions

1

Neutral current sensor input is required for 3 PH/4W or 1 PH/3W systems. For 3
PH/3W systems, do not make any connections.