Terminal assemblies are supplied with the
Entelliguard breaker. Fixed breakers have Back or
Front Connected Terminations available. This
instruction is for Back Connected Terminations



































Back Connected Terminations Assembly Procedure:

1. Turn the breaker off and discharge the closing springs

by depressing the OFF and ON buttons in the
sequence OFF-ON-OFF. Verify that the breaker OFF-
ON indicator shows OFF on a green background and
that the charge indicator shows DISCHARGE on a
white background.


2. Assemble the outer pole bottom & top Back

Connected Termination assemblies first to the breaker
rear terminal support & orient as shown in Fig A.


3. Terminal assemblies to be tightened with M12

hardware’s as shown in Fig A, to 80 Nm (59 ft-lbs)
torque.


4. Assemble the heat sinks LH & RH as shown in Fig B on

the outer poles first, and tightened them to 14 Nm
(10.3 ft-lbs) torque.


5. Repeat the above mounting procedure for remaining

adjacent poles.


6. Assemble remaining terminal assemblies similarly on

all the poles so as to populate as 3pole / 4 pole
breaker fig C & Fig D.


7. The bus bars to be supported within 200mm distance

and tightened to 80Nm (59 ft-lbs) torque.

Envelope

Size

Catalog #

Description TYPE

GBB360TBB3

Top side 3 pole

GBB360BBB3 Bottom

side 3

pole

GBB360TBB4

Top side 4 pole

Envelope 3

GBB360BBB4 Bottom

side 4

pole

EntelliGuard

®

G

Circuit Breaker

Accessories
Back Connected Terminations for Fixed
Breaker

WARNING: Before installing any accessories, turn the

breaker OFF, disconnect it from all voltage sources,

and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,

mettre le disjoncteur en position OFF, le déconnecter

de toute tension d’alimentation, et décharger les

resorts d’armement

DEH-41445 Installation Instructions

Top
terminal
Asm

Bottom
terminal
Asm

Nut plate

M12 hardware

M12 Spring
washer

M12 Plain
washer

Top
terminal
Asm

Bottom
terminal
Asm

Nut plate

M12 hardware

M12 Spring
washer

M12 Plain
washer

Fig A. Back Connected Terminations, Envelope 3 6000A

fixed

Table 1. Back Connected Terminations

Catalog numbers

1

Advertising