Function

ProTrip™ Trip Units are designed with interchangeable

Rating Plugs. These Rating Plugs change the per-unit

(1

X

) continuous-current rating of the breaker. A circuit

breaker equipped with a suitable Trip Unit and Rating

Plug has a long-time trip current equal to the ampere

rating marked on the Rating Plug times the LT setting on

the Trip Unit.
For example, a breaker frame with a 1600 A sensor, an 800

A Rating Plug, and a long-time pickup switch setting of 1.0

has an 800 A continuous-current (long-time) rating.
Several Rating Plugs are available for each sensor rating

and each Rating Plug is keyed for a particular sensor

rating.
The catalog number structure for the available Rating

Plugs for ProTrip conversion kits is listed in Table 1. See

DEH–40034, ProTrip™ Trip Units User’s Guide, for a

complete listing of all Rating Plug catalog numbers.

Front Label

The front label, shown in Figure 1, is visible when the

Rating Plug is installed. The items listed are:
Sensor Rating (S) The ampere rating of the

corresponding breaker frame.

Rating Plug

The Rating Plug continuous

Amps (X)

current in amperes.

Test

The test-jack receptacle is used with

the Test Kit, catalog number

TVRMS2, for overcurrent and

ground-fault functional testing.

Catalog Number

Follows the format PTppCqqqqGFD,

as shown in Table 1.

Figure 1. Rating Plug with ground-fault function.

PT 20 C 700 GFD

Code

Description

Function

Code

Description

Function

1

150 A

80

80 A

225

225 A

100

100 A

4

400 A

125

125 A

6

600 A

150

150 A

8

800 A

Sensor

225

225 A

16

1600 A

250

250 A

20

2000 A

300

300 A

30

3000 A

400

400 A

32

3200 A

450

450 A

40

4000 A

500

500 A

600

600 A

Rating

700

700 A

800

800 A

GFD

Ground Fault

Ground Fault

1000

1000 A

Defeatable

1100

1100 A

1200

1200 A

1500

1500 A

1600

1600 A

2000

2000 A

2400

2400 A

2500

2500 A

3000

3000 A

3200

3200 A

3600

3600 A

4000

4000 A

Table 1. Rating Plug catalog number structure.