Kit installation instructions – GE Industrial Solutions EntelliGuard E Network Interlock for 3200-5000 Ampere User Manual

Page 2

Advertising
background image

WARNING: Before installing any

accessories, turn the breaker

OFF

,

disconnect it from all voltage sources,

and discharge the closing springs.

AVERTISSEMENT: Tourner le

disjoncteur à la position

OFF

, le

débrancher de toute source de tension et

décharger les ressorts de fermeture avant

l’installation de tout accessoire.

Kit Installation Instructions

Use the following installation procedure for breakers
that were not equipped with a Network Interlock
accessory at the factory.

1. Open the circuit breaker and remove it from the

cubicle or substructure. Check to ensure the breaker

closing springs are DISCHARGED. (See User’s Guide

DEH202 or Maintenance Manual DEH204 for detailed

instructions.)

2. Carefully place the circuit breaker on a suitable

working surface, resting on the primary disconnects,

so that the bottom of the circuit breaker is accessible.

3. Assemble the trip paddle over the circuit breaker trip

shaft as shown in Figure 3. Secure the trip paddle to

the trip shaft using the # 10-32 screw and spring

washer provided. Install the # 8-32 adjusting screw and

nut as shown in Figure 3.

4. Assemble the Network Interlock mounting bracket to

the circuit breaker frame using two sets of 3/8-inch

countersunk bolts and washers as shown in Figure 4.

5. Fasten the Network Interlock module to the mounting

bracket using three sets of # 8-32 nuts, spring washers,

and flat washers as shown in Figure 5.

6. Ensure the Network Interlock is in the RESET state

(shown in Figure 7) by manually rotating the reset

lever counterclockwise. If the Network Interlock was

SET, this operation will cause the set lever to retract

(counterclockwise) away from the trip paddle.

7. With the breaker open, charge the breaker closing

springs. Do not close the breaker. Adjust the gap

between the set lever and the trip paddle by rotating

the adjusting screw as shown in Figure 7. The distance

between the set lever and the trip paddle must be

between 0.06 and 0.09 inch.

8. Manually push the set lever toward paddle, locking the

Network Interlock into the SET position (shown in

Figure 6). Check to ensure that this operation causes

the trip paddle to move.

9. Close the breaker by either depressing the close button

or activating the close coil circuit. The breaker should

not have closed since the Network Interlock was SET.

10. Fasten the manual reset assembly bracket to the

breaker frame using two sets of 1/4-inch hex-head

bolts and lock washers as shown in Figure

5.

11. Assemble the two reset rods as shown in Figure

5 and

Figure 6. Fasten the top end of the vertical rod to the

reset lever with two flat washers and one push nut as

shown Figure 6.

12. Pull the manual reset knob shown in Figure 5. Check

that the Network Interlock has returned to the RESET

state, as shown in Figure 7.

13. Charge and close the breaker. The breaker should

close properly since the Network Interlock is RESET.

14. Open the breaker. Connect six wires to the available

terminals on the Network Interlock device using the

crimp-on terminals provided. Connect two of the wires

to the NC and COM terminals of the microswitch as

shown in Figure 9.

15. Route the wires from the Network Interlock to the

secondary disconnect as shown in Figure 8 and secure

them with cable ties.

16. Using the spade terminals provided, connect a wire

from the trip and reset solenoids to terminals 15 and

20 of the secondary disconnect, respectively. Connect

the other two solenoid wires to terminal 21. Connect

the two microswitch wires to terminals 16 and 19.

Figure 10 shows the secondary disconnect numbering

scheme.

17. Reset the Network Interlock by pulling the manual

reset knob. The Network Interlock status circuit should

be open. Close the breaker manually or electrically.

The breaker should close properly.

18. Set the Network Interlock by applying 120 VAC across

terminals 15 and 21 on the secondary disconnect. The

breaker should trip open and the status circuit should

change from open to close.

19. Charge the breaker manually or electrically. Close the

breaker. The breaker should trip open, discharging

the closing springs.

20. Reset the Network Interlock by applying 120 VAC

across terminals 20 and 21 on the secondary

disconnect. The status circuit should change from

closed to open.

21. Charge and close the breaker. The breaker should

close properly.

22. Set the Network Interlock, and repeat Steps 17 through

21 five times.














Figure 3. Mounting the trip paddle assembly on the trip shaft

Trip Paddle

Trip Shaft

Adjusting Screw

1.62”

Advertising