GE Industrial Solutions Spectra Series Power Panelboards AFP6SKS User Manual

Spectra series™ power panelboards, General, Installation

Advertising
background image

g

Spectra Series™ Power Panelboards

Filler Plate Kit AFP6SKS

WARNING:

Danger of electrical shock or injury.

Turn

OFF power ahead of the panelboard or

switchboard before working inside the
equipment or removing any component

.

Do

not remove circuit protective devices or any
other component until the power is turned
OFF.

General

These instructions apply to the following catalog numbers:

•Filler plate kit AFP6SKS
•Circuit breaker types TKM, THKM, TK4V, TKL4V,

SKHA, SKLA, and SKPA

Installation

1. Install circuit breaker.

Install the circuit breaker

according to instruction sheet GEH-5623 for plug-in
construction or DEH-061 for bolt-on construction.

2. Install end filler plates.

For type TKM, THKM,

TK4V, TKL4, SKHA, SKLA, and SKPA circuit
breakers, place the lug covers, as listed in Table 1, on
the line and load ends of the circuit breaker, as
shown in Figure 1. Attach the end filler plates, as
listed in Table 2, to each side of the circuit breaker
with the #10-32 x

9

/

16

" screws provided. Tighten the

screws to 15 in-lb.

Breaker Type

Lug Cover

TKM, THKM

455C592P1, furnished with kit

TK4V, TKL4V

455C592P2, furnished with kit

SKHA, SKLA

Use covers furnished with breaker

SKPA*

Use covers furnished with breaker

* SKPA is available in 44"-wide panelboard or 45"-wide

switchboard construction only.

Table 1. Lug covers used with each breaker type.

Filler Plate

Switchboard or Panelboard

252B1768G2

40"-wide panelboard or switchboard

252B1768G1

44"-wide panelboard

252B1768G1

45"-wide switchboard

Table 2. End filler plates used with each panelboard or switchboard.

Figure 1. Installation of lug covers and filler plates.

GEH5629 Installation Instructions

R05

Filler
Plate

Filler
Plate

Lug

Cover

Lug

Cover

#10-32 Screws