12v microtlynx, 12a: non-isolated dc-dc power modules, Data sheet – GE Industrial Solutions 12V MicroTLynx 12A User Manual

Page 14: Safety considerations

Advertising
background image

GE

Data Sheet

12V MicroTLynx

TM

12A: Non-Isolated DC-DC Power Modules

4.5Vdc –14Vdc input; 0.69Vdc to 5.5Vdc output; 12A Output Current

May 2, 2013

©2013 General Electric Company. All rights reserved.

Page 14

Figure 41. Output ripple voltage for various output voltages
with external 1x10 µF, 1x47 µF, 2x47 µF or 4x47 µF ceramic
capacitors at the output (12A load). Input voltage is 12V.

Safety Considerations

For safety agency approval the power module must be
installed in compliance with the spacing and separation
requirements of the end-use safety agency standards, i.e., UL
60950-1, CSA C22.2 No. 60950-1-03, and VDE 0850:2001-12
(EN60950-1) Licensed.

For the converter output to be considered meeting the
requirements of safety extra-low voltage (SELV), the input must

meet SELV requirements. The power module has extra-low
voltage (ELV) outputs when all inputs are ELV.
The input to these units is to be provided with a fast-acting
fuse with a maximum rating of 15A in the positive input lead

.

0

10

20

30

40

50

60

70

0.5

1.5

2.5

3.5

4.5

5.5

Output Voltage(Volts)

R

ip

p

le(

m

V

p-

p)

1x10uF External Cap

1x47uF External Cap

2x47uF External cap

4x47uF External Cap

Advertising