GE Industrial Solutions 300_400 Line NEMA size 2 User Manual

Combination magnetic starters, Instructions for nema size 2, Geh-4776 instruction

Advertising
background image
































s

Max.Hp

For AC Motors

Max.
Volt-
age

Max.

Continous

Amp

Rating

AC Volts

Single-
Phase

Poly-
Phase

600

45

115
200
230

460/575

3

-

-

-

10
15
25

CAUTION:

Before installing in a nuclear

application, determine that the product is
intended for such use.

WARNING:

Disconnect power

before In-stalling or servicing.

DESCRIPTION

A General Electric 300-Line full voltage
magnetic combination starter consists of a
magnetic contactor with a three leg block
overload relay and a manually operated
circuit breaker or disconnect switch. The
disconnect switch may either be fusible or
non-fusible. The non-fusible disconnect
switch provides a means of manually
disconnecting the motor from the line. The
circuit breaker or fusible disconnect switch
provides motor branch short-circuit
protection. The overload relay provides,
motor protection against running and
stalled motor overload.

The overload relay is provided with a
yellow trip indicator which is located to
the right of the reset arm, and is visible
when the overload relay is tripped.

FEATURES

1.

Strongbox coil.

2. Overload relay, incorporates a dial for
±10% field adjustment of tripping current,
so that it is no longer necessary to change
heaters to eliminate such problems as
nuisance tripping in hot weather.
3.

Overload trip indicator.

4.

Straight through wiring.

5.

Oversized power terminals will

accommodate up to #4 wire.
6.

Starter can be disassembled and

inspected in a matter of seconds.
7.

Circuit breaker or disconnect switch is

mechanically interlocked with the
enclosure door to prevent opening the door
until the handle is moved to the OFF
position.

COIL REMOVAL

The encapsulated coil is impervious
to moisture, dirt, and oil. It resists
mechanical damage and failure due
to high humidity. No tools are
required to remove coil.
1.

Remove power from device.

2.

Press against coil while pulling up

slightly on coil retainers (A—Figure 1
or 2) and move retainers away from
coil.
3.

Withdraw magnet assembly, coil,

molded cover, and movable arm
from device.
4.

Withdraw spring clip (B—Figure 1

or 2) and remove armature from
movable arm.
5.

Remove coil from magnet.

6. Replace coil.
7.

Reassemble device by reversing

procedure.

2.

Clean magnet mating surfaces

of any dust or foreign matter.
3. Select heaters in accordance
with heater table, which
accompanies each device.
4.

Operate movable magnet and

operating arm by pressing on the
nameplate to assure free
movement.
5.

Mount the starter on a sturdy

vertical support.
6.

The overload relay may be reset

manually by depressing and
releasing the reset arm. Overload
relays with an optional normally
open contact are electrically
isolated from the normally closed
contact.

7.

Provide motor branch circuit

protection in accordance with the
National Electrical Code.

CONTACT REMOVAL

Movable contacts can be inspected
and replaced in seconds—without
tools (Figure 3).

RATINGS

INSTALLATION
Before connecting the starter:
1. Remove all packing.

These instructions do not purport to cover all details or variations in equipment not to provide for every possible contingency to
be met in connection with installation, operation or maintenance. Should further information be desired or should particular
problems arise which are not covered sufficiently for the purchaser’s purpose, the matter should be referred to the GE Company.

Instructions for
NEMA size 2

Combination
Magnetic Starters

CR307-CR308, CR310-CR311, CR387, CR390, CR407-CR408
CR410-CR415, CR487, CR490, CR492, CR494 Series

GEH-4776 Instruction