GE Industrial Solutions A-Series II Panelboards TEY User Manual
Page 2
Advertising
DEH40155
DEH40155 Rev.No.02
2
Figure 1. Installation of a TEY circuit breaker kit on left side of interior, catalog number
ASPP6EY12D, into an A-Series
®
II Panelboards.
5. Place the breaker as shown in fig.1 such that breaker strap hole aligns with
breaker mounting strap tapped hole and other end of breaker snaps with 3X base
lancing slot provided and then tighten terminal screws completely with 27-36 in-
lb.
6. Remove the eight screws [6] of existing two filler plates from dead front where
the TEY breaker needs to be installed, as illustrated in Figure 2