GE Industrial Solutions Spectra Series Power Panelboards AMC3KM and AMC2KM User Manual

Page 4

Advertising
background image

Attention – Procedure for Aluminum
Terminations

1.

Strip the insulation, being careful to not nick the wire.

2.

Clean the wire strands with a wire brush.

3.

Thoroughly coat the stripped conductor with a
suitable antioxidant compound, such as ALNOX or
PENETROX A13.

4.

Insert the conductor and tighten the connector screw
to the torque indicated on the rating label.

g

GE Industrial Systems

General Electric Company
41 Woodford Ave., Plainville, CT 06062

GEH5623 R04 0701

© 2001 General Electric Company

These instructions do not cover all details or variations in equipment nor do they provide for every possible contingency that
may be met in connection with installation, operation, or maintenance. Should further information be desired or should
particular problems arise that are not covered sufficiently for the purchaser’s purposes, the matter should be referred to the
GE Company.