Overview
The General Electric Distribution Cable Terminal Block
is a modular attachment primarily used to provide an
alternate means of connecting input/output signals
to Spectra

®

RMS Molded-Case Circuit Breakers with

microEntelliGuard

TM

or MicroVersaTrip

®

PM/Plus Trip

Units. The terminal block connection points are as
follows:

Spectra

®

RMS Breaker with microEntelliGuard

TM

or

MicroVersaTrip

®

PM Trip Unit

• Control power (+24vdc)
• Control power (-common)
• System communications (Comm. +)
• System communications (Comm. -)
• Breaker position (Aux. Switch red)
• Breaker position (Aux. Switch white)
• Voltage A φ (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• Voltage B φ (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• Voltage C φ (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• Neutral current sensor - black (for equipment

ground fault)

1

• Neutral current sensor - white (for equipment

ground fault)

1

Spectra

®

RMS Breaker with MicroVersaTrip

®

Plus or

microEntelliGuard

TM

(with Basic Metering) Trip Unit

• Control power (+24vdc)
• Control power (-common)
• Neutral current sensor - black (for equipment

ground fault)

1

• Neutral current sensor - white (for equipment

ground fault)

1

GEH-6257 Installation Instructions

Distribution Cable

Terminal Block

For Spectra

®

RMS Molded-Case Circuit Breakers

with microEntelliGuard

TM

, MicroVersaTrip

®

PM or MicroVersaTrip

®

Plus Trip Units

For Catalog Number SDCTBA11

Circuit Breaker Accessory

GE Energy

Industrial Solutions

1

Neutral current sensor input is required for 3Ø/4W or 1Ø/3W systems.
For 3Ø/3W systems do not make any connections.