GE Industrial Solutions EntelliGuard G Flat front Terminations Envelope 1 & 2 User Manual

Entelliguard

Advertising
background image

1

Flat front Terminations
Envelope 1 & 2

Flat Front Terminal assemblies are supplied with
the Entelliguard breaker when needed

























Catalogue No:

Catalog #

Description

GBB1TBF3

Envelope 1-3pole 800 - 2000A

GBB1TBF4

Envelope 1-4pole 800 - 2000A

GBB2TBF3

Envelope 2-3pole 800A - 3000A

GBB2TBF4

Envelope 2-4pole 800A - 3000A

GBB1STBF3 Envelope 1-3pole Type S up to 1200A

GBB1STBF4 Envelope 1-3pole Type S up to 1200A


















Flat Front Terminations Assembly Procedure:

1. Turn the breaker off and discharge the closing

springs by depressing the OFF and ON buttons in
the sequence OFF-ON-OFF. Verify that the
breaker OFF-ON indicator shows OFF on a green
background and that the charge indicator shows
DISCHARGE on a white background.


2. Assemble the Flat Front to the rear terminals with

M12 Hardware as shown in Fig A., Tighten the
hardware to torque 50N-m (36.9 ft-lbs)

3. Assemble the Heat Sink with M8 Hardware to Flat

Front as shown in Fig A. Tighten to torque 12-
14N-m (8.9-10.3 ft-lbs)



4. Similarly populate the Flat Front and Heat sink on

all other terminals as shown in fig B & C.


5. The bus bars to be supported within 200mm

distance and tightened to 50N-m (36.9ft-lbs)
torque.



EntelliGuard

®

G

Circuit Breaker

Accessories

Flat Front Terminations for Fixed
Breaker

WARNING: Before installing any accessories, turn the
breaker OFF, disconnect it from all voltage sources,
and discharge the closing spings.

AVERTISSEMENT: Avant d’installer tout accessoire,
mettre le disjoncteur en position OFF, le déconnecter
de toute tension d’alimentation, et décharger les
resorts d’armement

DEH- 41405 Installation Instructions

Fig A. Flat front Termination assembly