Electrical specifications, Isolation specifications, General specifications – GE Industrial Solutions FNW700R Series User Manual

Page 3: Continued)

Advertising
background image

Data Sheet
October 24, 2011

FNW700R Power Modules; DC-DC Converters

36 – 75 Vdc Input; 28Vdc Output; 700W Output

LINEAGE

POWER

3

Electrical Specifications

(continued)

Parameter

Device

Symbol

Min

Typ

Max

Unit

Output Voltage Set-point
(V

IN

=V

IN,nom

, I

O

=I

O, max

, T

c

=25°C)

All V

O, set

27.5 28 28.5 V

dc

Output Voltage
(Over all operating input voltage, resistive load,
and temperature conditions until end of life)

All V

O

27.15

28.85

V

dc

Output

Regulation

Line (V

IN

=V

IN, min

to V

IN, max

) All

0.05 0.2 %V

o

Load (I

O

=I

O, min

to I

O, max

) All

0.05 0.2

%V

o

Temperature (T

c

= -40ºC to +100ºC)

All

100 300 mV

Output Ripple and Noise on nominal output

(V

IN

=V

IN, nom

and I

O

=I

O, min

to I

O, max

)

RMS (5Hz to 20MHz bandwidth)

All

80

mV

rms

Peak-to-Peak (5Hz to 20MHz bandwidth)

All

300

mV

pk-pk

External Capacitance
Note: use a minimum 470uF output capacitor. If
the ambient temperature is less than -20

0

C, use

more than 3 of recommended minimum
capacitors.

All C

O, max

470 1000 5000

μF

Output Current

All

I

O

2

25

A

dc

Output Current Limit Inception

All

I

O, lim

26

29 32 A

dc

Efficiency
V

IN

=V

IN, nom

, T

c

=25

0

C

I

O

=I

O, max ,

V

O

= V

O,set

All

η

90

%

Switching Frequency

f

sw

300

kHz

Dynamic Load Response

(

I

O

/

t=1A/10s; V

in

=V

in

,

nom

; T

c

=25°C; Tested

with a 470 μF aluminum and a 10 µF ceramic

capacitor across the load.)

Load Change from I

O

= 50% to 75% of I

O,max

:

Peak Deviation

Settling Time (Vo<10% peak deviation)

All

V

pk

t

s

__

3
2

__

%V

O, set

ms

Load Change from I

O

= 75% to 50% of I

o,max

:

Peak Deviation

V

pk

__ 3 __

%V

O, set

Settling Time (Vo<10% peak deviation)

t

s

2

ms

Isolation Specifications

Parameter

Symbol

Min

Typ

Max

Unit

Isolation Capacitance

C

iso

1500

pF

Isolation Resistance

R

iso

10

MΩ

General Specifications

Parameter

Device

Symbol

Min

Typ

Max

Unit

Calculated Reliability based upon Telcordia SR-
332 Issue 2: Method

I

Case 3 (I

O

=80%I

O, max

,

T

A

=40°C, airflow = 200 lfm, 90% confidence)

All

FIT 405.4

10

9

/Hours

MTBF 2,466,797 Hours

Weight All

150

g

(5.3) (oz.)

Advertising