GE Industrial Solutions TJH-TJL with MicroVersaTrip Plus User Manual

Molded-case circuit breakers, Introduction, Lug selection

Advertising
background image

Introduction

This publication contains information on mounting
dimensions, lugs, internal and external accessories, and
trip unit and rating plug selection for K Frame molded-
case circuit breakers. It also describes the installation of
neutral current sensors for ground-fault protection.

Lug Selection

Circuit breakers are provided without lugs. The available
lugs are listed in Table 1.

Wire ranges are as follows:

• TCAL43: (1) 6–600 MCM or (2) 2/0–250 MCM

• TCOL43: (1) 6–600 MCM or (2) 2/0–250 MCM

• TCAL63: (2) 4/0–350 MCM Cu or (2) 300–500 MCM Al

• TCOL63: (2) 250–350 MCM

Frame

Type

Sensor Rating

(Amps)

Rating Plug

(Amps)

Standard Lugs
Cu/Al Cat. No.

Optional Lugs

Cu Cat. No.

150

J400

300

All available

TCAL43

TCO43

400

J600

600

300, 400

TCAL43

TCO43

450, 500, 600

TCAL63

TCO63

Table 1. Catalog numbers of available lugs.

g

Molded-Case Circuit Breakers

MicroVersaTrip Plus™ Trip Unit in TJH1S, TJH4S,
TJH6S, TJL1S, TJL4S, and TJL6S Breakers

GEH–5397A