Related publications, Estimated time to complete tasks, General description – GE Industrial Solutions Neutral Rogowski Current Transformer (CT) User Manual

Page 3: Akd-5—neutral disconnect assembly (breaker—n/a)

Advertising
background image

2

Neutral Assemblies Manual

DEH-41531 02/12

Related Publications

Publication

Publication Number

Brochure

DEA-532

Snapshot

DEE-543

Installation Manual AKD8

DEH-41549

Installation Manual AKD6

DEH-41548

Installation Manual AKD5

DEH-41547

Accessory: Door Interlock (Door Interlock Kit)

DEH-41529

Accessory Retrofill Doors Assembly

DEH-41563

Accessory: Position Switch Plate & Position Switch
Assembly & Wiring (Position Switch Kit)

DEH-41530

Accessory: Neutral Rogowski CT Disconnect
(Neutral Assemblies)

DEH-41531

Accessory: Programmer Disconnects

DEH-41532

Accessory: Finger Clusters (Cluster Assemblies)

DEH-41533

Accessory: Secondary Disconnects

DEH-41534

FAQ

DEQ-171

Application Guide

DET-753

Guideform Spec

DET-754

Spare/Renewal Parts Guide

DET-755

Estimated Time to Complete Tasks

It takes about 20 minutes to install or replace the assembly.

General Description

When a legacy AK breaker is replaced with a retrofitted EntelliGuard ACB, the incoming wires from the neutral
CT’s need to be routed to the cassette secondary disconnects directly.

AKD-5—Neutral Disconnect Assembly (Breaker—N/A)

When a legacy AK breaker is replaced with a retrofitted EntelliGuard ACB, the incoming wires from the neutral
CT’s need to be routed to the cassette secondary disconnects directly.

AKD-5—Replace Iron Core Neutral CT with a Rogowski (Compartment)

The

AKD-5 EntelliGuard R Circuit Breaker uses an open-core Rogowski current sensor to measure current level

vs. an iron-core style (

Figure 1

) used in the legacy AK, AKR breakers. For the retrofill to calculate the current levels on

a 4 wire circuit, the neutral iron-core CT in the cable compartment needs to be replaced with a Rogowski style CT.
The current transformer comes with the CT-mounted on copper bars matching the same hole-pattern as the existing
neutral bar. The existing wires can be reused. Note, if existing wires need to be replaced, then a continuous wire runs
from the CT to the neutral disconnect in the cubicle.