A series – GE Industrial Solutions A Series Lighting Control Panelboards BACnet Protocol User Manual

Page 4

Advertising
background image

A Series

®

Lighting Controller

BACnet Protocol Implementation Conformance Statement

4

Object-Type

Supported

Dynamically

Creatable

Dynamically

Deletable

Optional Properties Supported Writable Properties

Binary Input

;

;

;

Description, Device Type,
Reliability, Active Text, Inactive
Text, Change Of State Time,
Change Of State Count, Time
of State Count Reset

Object Name, Description,
Polarity, Present Value
(conditional), Out of Service,
Reliability (conditional)

Binary Output

;

;

;

Description, Device Type,
Reliability, Active Text, Inactive
Text, Change Of State Time,
Change Of State Count, Time
of State Count Reset, Min On
Time, Min Off Time

Object Name, Description,
Present Value, Polarity,
Relinquish Default, Min On
Time, Min Off Time, Out of
Service, Reliability
(conditional)

Binary Value

;

;

;

Description, Reliability, Active
Text, Inactive Text

Object Name, Description,
Present Value (conditional),
Out of Service, Reliability
(conditional)

Calendar

;

;

;

Description

Object Name, Description,
Date List

Command

†

†

†

Device

;

N/A

N/A

Description, Location, APDU
Seg Timeout, Time Synch
Recipients, Max Master, Max
Info Frames, Max Segments
Accepted, Local Time, Local
Date, UTC Offset, DST Status,
Active COV Subscription,
Backup Failure Timeout, Last
Restore Time, Configuration
Files

Object Name, Description,
Location, Time Synch
Recipients, UTC Offset, APDU
Segment Timeout, APDU
Timeout, Number of APDU
Retries, Max Master, Max Info
Frames

Event

Enrollment

;

;

;

Description, Notification Class

Object Name, Description,
Event Type, Event Parameters,
Object Property Reference,
Event Enable, Notification
Class

File

;

†

†

Description

Object Name, Description, File
Type, Archive

Group

†

†

†

Life Safety

Point

†

†

†

Life Safety

Zone

†

†

†

Loop

;

;

;

Description, Reliability, Update
Interval, Proportional
Constant, Proportional Units,
Integral Constant, Integral
Units, Derivative Constant,
Derivative Units, Bias,
Maximum Output, Minimum
Output, COV Increment

Object Name, Description,
Action, Manipulated Var Ref,
Controlled Variable Ref,
Controlled Var Units, Setpoint,
Setpoint Ref, Proportional
Constant, Proportional
Constant Units, Integral
Constant, Derivative Constant,
Bias, COV Increment, Out of
Service, Present Value
(conditional), Reliability
(conditional)

Multistate

Input

;

;

;

Description, Reliability, Device
Type, State Text

Object Name, Description,
Present Value (conditional),
Out of Service, Reliability
(conditional)

Multistate

Output

†

†

†

Advertising