GE Industrial Solutions Sealable Trip Unit Cover User Manual

Sealable trip unit cover, Geh-707 installation instructions, Ge energy industrial solutions

Advertising
background image

WARNING: Danger of electrical shock or injury. Turn
power OFF ahead of the device before installation or
modification. Do not remove circuit protective devices
until the power is OFF.

Introduction
These instructions cover the installation of the sealable,
clear plastic cover for Spectra

®

RMS SG and SK frame

circuit breakers with microEntelliGuard

TM

trip units, as

shown in Figure 1.

Sealing the cover in accordance with the National
Electrical Code, paragraph 240-6 exception and
paragraph 240-82, allows an ampere rating equal to
the adjusted long-time pickup setting (current setting)
and therefore permits conductors to be sized to the
setting. The cover also prevents removal and changing
of the rating plug.

Figure 1. Sealable trip unit cover installed on a Spectra® RMS

circuit breaker

GEH-707 Installation Instructions

Sealable Trip Unit Cover

For Spectra

®

RMS Molded-Case Circuit Breakers

with microEntelliGuard

TM

Trip Units

For Catalog Numbers SPCOV1C, SPCOV3C

GE Energy

Industrial Solutions

Advertising