WARNING: Danger of electrical shock or injury. Turn
power OFF ahead of the device before installation or
modification. Do not remove circuit protective devices
until the power is OFF.
Introduction
These instructions cover the installation of the sealable,
clear plastic cover for Spectra
®
RMS SG and SK frame
circuit breakers with microEntelliGuard
TM
trip units, as
shown in Figure 1.
Sealing the cover in accordance with the National
Electrical Code, paragraph 240-6 exception and
paragraph 240-82, allows an ampere rating equal to
the adjusted long-time pickup setting (current setting)
and therefore permits conductors to be sized to the
setting. The cover also prevents removal and changing
of the rating plug.
Figure 1. Sealable trip unit cover installed on a Spectra® RMS
circuit breaker
GEH-707 Installation Instructions
Sealable Trip Unit Cover
For Spectra
®
RMS Molded-Case Circuit Breakers
with microEntelliGuard
TM
Trip Units
For Catalog Numbers SPCOV1C, SPCOV3C
GE Energy