Electrical Data

Table 1 contains the electrical specifications for the motor-
operated mechanism.

Control

Timing (Sec)

Catalog

No.

Volts

In-Rush

Amps

Running

Amps

Closing

Opening

Reset

Recommended

Fuse

SEMOM1

120 Vac

10.5

5.0

SFMOM1 125 Vdc

13.5

4.0

1 Amp

SEMOM2

SFMOM2

240 Vac

6.5

3.0

.15

.13

Time Delay

SEMOM8

SFMOM8

24 Vdc

31

15.5

2 Amp

SEMOM9

SFMOM9

48 Vdc

20

7.0

Time Delay

Table 1. Electrical specifications.

Installation

WARNING: The circuit breaker must be de-energized
before the motor operator is installed.

1. Mount the circuit breaker using the diagonal

mounting screw locations.

2. Connect the line and load circuit breaker terminals.

3. Install the motor operating mechanism using the

remaining diagonal mounting screw locations,
shown in Figure 2. See Figure 3 for alternate
mounting methods.

4. Align the racking mechanism and the circuit

breaker handle by rotating the lead screw or by
moving the breaker handle. Close the cover.

5. Electrically test the mechanism according to the

specifications in Table 1. Refer to Figure 5 for a
schematic and auto reset diagram.

Figure 3. Breaker mounting methods.

Figure 2. Mounting the motor-operated mechanism on the breaker.

10-32 x 4.25 Screw (E Frame)

10-32 x 6 Screw (F Frame)

Lock

Washer

Nut

Flat Washer

Breaker Supported

by Bus Structure

Breaker Supported

Type

SF250

Mounting

Screws

Type

SE150

Mounting

Screws

Rotate Lead

Screw Assembly

to Align Racking
Mechanism with

Circuit Breaker

Handle

Move Shutter

if Necessary