Entelliguard, 1 introduction, 2 safety – GE Industrial Solutions EntelliGuard E Test Cabinet User Manual

Page 4: 3 maintenance

Advertising
background image

4

EntelliGuard

TM

E Breaker Test Cabinet

Section 1. Introduction

1-1 Introduction

This manual provides the information needed by the user

to properly install, operate and maintain the Test Cabinet.

1-2 Safety

Each user must maintain a safety program for the

protection of personnel, as well as other equipment, from

the potential hazards associated with electrical

equipment.

The following requirements are intended to augment the

user’s safety program, but NOT supplant the user’s

responsibility for devising a complete safety program. The

following basic industry practiced safety requirements

are applicable to all major electrical equipment such as

switchgear or switchboards. GE neither condones nor

assumes any responsibility for practices which deviate

from the following:

1. ALL CONDUCTORS MUST BE ASSUMED TO BE

ENERGIZED UNLESS THEIR POTENTIAL HAS BEEN

MEASURED AS GROUND AND SUITABLE GROUNDING

CONDUCTORS HAVE BEEN APPLIED TO PREVENT

ENERGIZING. Many accidents have been caused by

back feeds from a wide variety of sources.

2. Although interlocks to reduce some of the risks are

provided, the individual’s actions while performing

service or maintenance are essential to prevent

accidents. Each person’s knowledge; his mental

awareness; and his planned and executed actions

often determine if an accident will occur. The most

important method of avoiding accidents is for all

associated personnel to carefully apply a thorough

understanding of the specific equipment from the

viewpoints of its purpose, its construction, its

operation and the situations that could be

hazardous.

All personnel associated with installation, operation and

maintenance of electrical equipment, such as power

circuit breakers and other power handling equipment,

must be thoroughly instructed, with periodic retraining,

regarding power equipment in general as well as the

particular model of equipment with which they are

working. Instruction books, actual devices and

appropriate safety and maintenance practices such as

OSHA publications, National Electric Safety Code (ANSI

C2), the National Electric Code, and National Fire

Protection Association (NFPA) 70B Electrical Equipment

Maintenance must be closely studied and followed.

During actual work, supervision should audit practices to

assure conformance.

1-3 Maintenance

Excellent maintenance is essential for reliability and

safety of any electrical equipment. Maintenance

programs must be tuned to the specific application, well

planned and carried out consistent with both industry

experience and manufacturer’s recommendations. Local

environment must always be considered in such

programs, including such variables as ambient

temperatures, extreme moisture, number of operations,

corrosive atmosphere or major insect problems and any

other unusual or abusive condition of the application.

One of the critical service activities, sometimes neglected,

involves the calibration of various control devices. These

monitor conditions in the primary and secondary circuits,

sometimes initiating emergency corrective action such as

opening or closing circuit breakers. In view of the vital

role of these devices, it is important that a periodic test

program be followed. As was outlined above, it is

recognized that the interval between periodic checks will

vary depending upon environment, the type of device

and the user’s experience. It is the GE recommendation

that, until the user has accumulated enough experience

to select a test interval better suited to his individual

requirements, all significant calibrations be checked at an

interval of one to two years.

To accomplish this, some devices can be adequately

tested using test sets. Specific calibration instructions on

particular devices typically are provided by supplied

instruction books.

Instruction books supplied by manufacturers address

components that would normally require service or

maintenance during the useful life of the equipment.

However, they cannot include every possible part that

could require attention, particularly over a very long

service period or under adverse environments.

Maintenance personnel must be alert to deterioration of

any part of the supplied switchgear, taking actions, as

necessary to restore it to serviceable status.

Industry publications of recommended maintenance

practices such as ANSI/NFPA 70B, Electrical Equipment

Maintenance, should be carefully studied and applied in

each user’s formation of planned maintenance.