A synopsis of the C-2000 line's broad scope
Standards and Listings
IEC 947-1
BS 5424
CSA C.22.2/14
IEC 947-4
BS 775
EN 50005
IEC 158-1
CEI 17-3/252
UNE 20109
CENELEC HD 419
ASE 1025
VDE 0660/102
NFC.63-110
UL 508
CE Mark
Pending Standards
SEMKO, NEMKO, DEMKO, Lloyds Register
and Listings
Ambient Temperature
Operating
-13˚ to +131˚F / -25˚ to +55˚C
Storage
-58˚ to +176˚F / -50˚ to +80˚C
Altitude Derating
Up to 10,000 ft.
Nominal Values
(3,000 m)
10,000 to 13,200 ft.
90% rated current
(3,000 to 4,000 m)
13,200 to 16,000 ft.
80% rated current
(4,000 to 5,000 m)
Maximum Rated Voltage
600 VAC
Mounting Position
3-Pole and 4-Pole
To maintain operating integrity, the contactor must be mounted in one of the
CL Contactors
positions shown below:
(5-75 hp)
3-Pole and 4-Pole
The contactor must be installed vertically or tilted a maximum of 30˚ from vertical,
CK Contactors
as shown below:
(100-500 hp)
General Specifications