Indicators, Panel mounting switch, Jumpers – GE Industrial Solutions A Series Lighting Control Panelboards nstallation and Wiring User Manual

Page 5

Advertising
background image

5

Indicators

The LED indicators on the lighting controller and their
functions are listed in Table 2.

LED

Function

Description

Network

(Ethernet)

Ethernet Communication Status
Indicators LNK and ACT

One LED (LNK) turns on to indicate a cable link is successfully
established, and another green LED (ACT) flashes to indicate
network activity (incoming or outgoing data) on the port.

Power

Device Power Indicator

This amber LED is lit when control power is present on the device.
If no control power transformer is connected, the LED is off.

Scan

CPU Scan Indicator

This red LED flashes at a rate relative to the CPU scan rate of the
database within the controller.

Network

(NET1)

RS-485 Communication Status
Indicators for NET1

A green LED flashes to indicate when the device is transmitting
out the associated port and a red LED flashes to indicate when
the device is receiving data through the port.

Network

(NET2)

RS-485 Communication Status
Indicators for NET2

A green LED flashes to indicate when the device is transmitting
out the associated port and a red LED flashes to indicate when
the device is receiving data through the port.

Alarm Output

(BO68)

Output Status Indicator

If the output is activated, a green LED is lit. If the output is not
activated, the LED is off.

Table 2. LED indicators on the lighting controller.

Panel Mounting Switch

The panel-mounting switch, illustrated in Figure 5,
provides the ability to mount the circuit breaker panel
“Service from top” or “Service from bottom.” If the panel
is mounted right-side up (the connectors along the
bottom of the board), the switch should be set to

NORM

(default). If the panel is mounted upside down (the
connectors along the top of the board), the switch should
be set to

FLIP

. This insures correct breaker addressing.

This switch is located near the NET2 connector.

Figure 5. Panel mounting switch.

Jumpers

This section describes the jumper settings on the lighting
controller.

Input Signal Type Jumper

The input type is selected by placing the jumper,
illustrated in Figure 6, in the correct location on the Input
Type Selector Block. The figure shows the factory default
selection of 10 k

Ω.

• 4–20 mA – for sensors that output a 4–20 mA signal
• 10K – Internally powered for resistance and dry

contact measurement.

• 5V – For sensors that output a 0–5 Vdc signal
• 10V – For sensors that output a 0–10 Vdc signal

Figure 6. Input signal type jumper.

SRAM Memory Clear Jumper

This jumper, illustrated in Figure 7, is provided to clear
the controller database (SRAM). The two positions
function as follows:

• RUN

– The battery is connected in the circuit and

maintains SRAM memory, even when 24 Vac power is
removed from the controller, thereby maintaining
both the integrity of the database and the internal
time of the on-board real-time clock (for as long as
the battery lasts). This jumper position is required
before applying power for the device to operate
properly.

• CLEAR

– When the jumper is moved to the CLEAR

position (only when the power is off), the SRAM
memory is cleared, deleting the database but not
resetting the internal time of the on-board real-time
clock. This jumper position is recommended if the
product will be stored for prolonged periods. The
database will be loaded from flash memory.

Figure 7. SRAM memory clear jumper.

Device Type Jumper

This jumper, illustrated in Figure 8, configures the
lighting controller as one of several device types,

Advertising