Function
EntelliGuard TU Trip Units are designed with UL-Listed
interchangeable rating plugs. These rating plugs
change the per-unit (1X) continuous current rating of
the breaker. A circuit breaker frame equipped with a
suitable rating plug has a long-time trip value equal
to the ampere rating marked on the rating plug. For
example, a breaker frame with a 1600 A sensor and
an 800 A rating plug has an 800 A continuous current
(long-time) rating.

The available rating plugs for the AKR , Power Break,
WavePro and EntelliGuard families are listed in Table 1.
Not all sensors listed in Table 2 are available in all circuit
breakers.

Table 1. Rating plug catalog numbers

GTP0060U0101

GTP1100U1225

GTP0080U0101

GTP1200U1232

GTP0100U0103

GTP1500U1640

GTP0125U0103

GTP1600U1640

GTP0150U0104

GTP1900U2050

GTP0200U0204

GTP2000U2050

GTP0225U0306

GTP2200U2550

GTP0250U0407

GTP2400U2564

GTP0300U0408

GTP2500U2564

GTP0350U0408

GTP3000U3064

GTP0400U0410

GTP3200U3264

GTP0450U0612

GTP3600U4064

GTP0500U0613

GTP4000U4064

GTP0600U0616

GTP5000U5064

GTP0700U0816

GTP6000U6064

GTP0750U0820

GTP1600K4040*

GTP0800U0820

GTP2000K4040*

GTP0900U1020

GTP3000K4040*

GTP1000U1025

GTP4000K4040*

* For use with ITE 4000A conversion kits ONLY

Front Label

Figure 1. Front of rating plug, showing label

The front label, shown in Figure 1, is visible when the
rating plug is installed. The items listed are:
Rating Plug Amps (X) The rating plug continuous

current in amperes

Catalog Number

GTP1100U1225

In this example:
GTP
= EntelliGuard TU trip unit rating plug

1100 = The rating plug continuous current in amperes

U = Universal Trip Plug (Use K for ITE 400A sensor

conversion kit)

12 = Smallest sensor that accepts this plug (1200A)

25 = Largest sensor that accepts this plug (2500A)

Table 2. Catalog number sensor rating designations

Sensor Designation

Sensor Rating

01

150A

02

200A

03

225A

04

400A

06

600A

07

630A

08

800A

10

1000A

12

1200A

13

1250A

16

1600A

20

2000A

25

2500A

30

3000A

32

3200A

40

4000A

50

5000A

60

6000A

64

6400A

DEH-41318 Installation Instructions

EntelliGuard

®

TU Rating Plugs

For Power Break

®

, Power Break

®

II, AKR, WavePro

®

,

EntelliGuard

®

G / microEntelliGuard

TM

Circuit Breakers and Trip Unit Conversion Kits

GE Energy