GE Industrial Solutions SDCJBBC User Manual

Advanced distribution cable junction box, Geh-704 installation instructions, Ge energy industrial solutions

Advertising
background image

Overview
The General Electric Advanced Distribution Cable
Junction Box is a modular connector used to provide
quick, easy and reliable attachment of Spectra

®

RMS

Molded-Case Circuit Breakers with microEntelliGuard

TM

Trip Units to the Distribution Cable System. The
electronic signals supported by the Advanced
Distribution Cable Junction Box appear below.

Input/output signals to Spectra

®

RMS Breaker with

microEntelliGuard

TM

Trip Unit

• control power (+24vdc)
• control power (common)
• voltage A f (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• voltage B f (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• voltage C f (must be from Voltage Module or Voltage

Conditioner Plate or Voltage Conditioner Assembly)

• neutral current sensor - black (for equipment ground

fault)

1

• neutral current sensor - white (for equipment ground

fault)

1

• breaker position (via installed aux. switch - red wire)
• breaker position (via installed aux. switch - white wire)
• system communications (Comm +)
• system communications (Comm –)
• zone select interlock (ZSI O –)
• zone select interlock (ZSI O +)
• zone select interlock (ZSI I –)
• zone select interlock (ZSI I +)
• reduced energy let-through (RELT I –)
• reduced energy let-through (RELT I +)
• ground fault alarm (GFA/PC1 O –)
• ground fault alarm (GFA/PC1 O +)
• reduced energy let-through (RELT/PC2 O –)
• reduced energy let-through (RELT/PC2 O +)

GEH-704 Installation Instructions

Advanced Distribution Cable

Junction Box

For Spectra

®

RMS Molded-Case Circuit Breakers

with Advanced Feature microEntelliGuard

TM

Trip Units

For Catalog Number SDCJBBC

Circuit Breaker Accessory

GE Energy

Industrial Solutions

1

Neutral current sensor input is required for 3Ø /4W or 1Ø /3W systems. For 3Ø /3W systems, do not make any connections.