GE Industrial Solutions Spectra G-Frame MCCB with microEntelliGuard trip unit User Manual

Page 4

Advertising
background image

GEH-700 Installation Instructions

For individual front panel mounting:
1. Drill and tap all mounting holes and make any

necessary front-panel escutcheon cutouts, as
shown in Figure 1.

Figure 1. Mounting Hole and Escutcheon Cutout Pattern in/(mm)

2. Mount the breaker with the hardware described in

Table 5, following the instructions supplied with the kit.

Table 5. Breaker Mounting Screw Kits

Catalog Number Application

Kit Description

SFGMSK1

Mounting plate with

tapped holes

Four #12-24x3-3/4

screws and lock

washers

SFGMSK2

Mounting plate with

clearance holes

Four #12-24x4-1/4

screws, nuts, and lock

washers

For GE switchboard and panelboard mounting:
Install the breaker into the equipment according to the
instructions supplied with the equipment. Available
mounting hardware kits are listed in Table 6.

Table 6. Equipment Mounting Hardware Kits

Equipment

Double Branch Single Branch

Panelboard-Spectra Series

AMC6GBFP

AMC3GMFP

Switchboard – Spectra Series

class 1 and 2

AMC6GBFP

AMC3GMFP

Switchboard – AV1, AV2

N/A

N/A

Switchboard – AV3, AV5

N/A

ContactFactory

For individual mounting in a GE enclosure:
Install the breaker according to the instructions
supplied with the enclosure. Available enclosures
are listed in Table 7 (refer to the BuyLog for other
accessories and/or any enclosure limitations).

Table 7. Enclosures

Enclosure Type

400A Catalog No. 600A Catalog No.

NEMA 1 (indoor)

SG400F

SG400S

SG600F

SG600S

NEMA 3R (outdoor)

SG400R

SG600R

NEMA 12 (oil-tight and

dust-tight)

SG400J

SG600J

Setup and Adjustment
The Spectra RMS microEntelliGuard

TM

trip units are

digital, rms sensing, electronic trip units with an LCD
and keypad for viewing and/or changing the various
function settings. Refer to User’s Manual GEH-702
for detailed information concerning the operation,
adjustment, and setting of the breaker trip unit.

You should record the overcurrent protection and
protective relay set points for future reference.

NOTE: Trip units as received may have settings that are
undesirable for the specific application. Ensure that
settings are appropriately adjusted before energizing
the breaker.

Operation
The circuit breaker status is indicated by ON/OFF
markings, universal I/O symbols, and an indicator
window that shows red for ON, yellow for TRIP, and
green for OFF. The corresponding handle positions are
illustrated in Figure 2. To close the breaker from the
OFF position, move the handle to the ON position. To
close the breaker from the TRIP position, first move the
handle to the OFF (reset) position, and then back to the
ON position.

A Push-To-Trip button is provided for convenience in
testing the mechanical operation of the breaker.